Prog mode, Menu structure, Main menu – Greenheck Vari-Green Control - Constant Pressure/Air Flow Control (479653) User Manual

Page 6

background image

Constant Press

Control Mode

Constant Airflow

Control Mode

Setpoint

Location: Remote

1.00 in WC

Maximum Setpoint

2 to 10 VDC

Remote Setpoint

-1.00 in WC

Minimum Setpoint

0 to 10 VDC

Remote Setpoint

10,000 CFM

Maximum Setpoint

2 to 10 VDC

Remote Setpoint

0 CFM

Minimum Setpoint

0 to 10 VDC

Remote Setpoint

Measurement

Device: Pitot

Measurement

Device: AMS

4.00 sq ft

Duct Area

2,000

AMS “K” Value

0.5000

AMS “m” Value

1.00

Air Density Corr

1.00

Pitot Correction

0 to 10 VDC

Control Output

2 to 10 VDC

Control Output

0 seconds

Sensor Filter

3 seconds

Startup Timer

Fast

Response Time

Inlet

Fan Control on:

Outlet

Metric

Units of Measure

Imperial

Units of Measure

Save

SET

K = 4005

m = 0.5

0 to 10 VDC

Airflow Output

2 to 10 VDC

Airflow Output

0 to 10 VDC

Pressure Output

2 to 10 VDC

Pressure Output

IF

Pressure Sensor

=

Internal

IF

Pressure Sensor

=

Remote

1.00 in WC

Rem Sensor Max

-1.00 in WC

Rem Sensor Min

Setpoint

Location: Local

Medium

Response Time

Slow

Response Time

Enter to Select

Initial Setup

Setpoint

Location: Remote

Setpoint

Location: Local

5000 CFM

Max Flow Output

Fan Control on:

1 - Initial Setup – select this menu
to change settings related to the
application of the control, such as:

• Pressure or airflow mode
• Local or remote setpoint
• Fan inlet or outlet control

The

Setpoint Edit menu (pg. 8) is

then used to adjust the common
setpoints, such as:

• Pressure or airflow mode
• Cutout settings
• Min/max output %
• Override, digital output %

PROG Mode:

Set the control to program mode to
adjust initial settings and setpoints.
A manual mode also exists to
manually set the output of the
control.

Menu Structure

The structure of the program menu is
shown below. A detailed description
of the parameters follows
the diagram.

1-

2-

3-

4-

Main Menu

Initial Setup Enter to

select

IF

Setpoint = Local

AND

Control Mode = Constant Pressure

IF

Setpoint = Local

AND

Control Mode = Constant Airflow

Pressure Setpnt

-0.010 in WC

Cutout Setpoint Fan

Speed: 20.8%

Cut Ret Pres Set

0.010 In. WC

30 Seconds

Cutout Delay

Airflow Setpoint

5000 CFM

20%

Minimum Output %

100%

Override Out %

100%

Maximum Output %

100%

Dig Output Set

Save

Manual Out: 50%

Ps: 0.00 in WC

Restore Factory Defaults:

No

YES

Are you sure?

Exit

IF

Setpoint = Remote

IF

Control Mode = Constant Pressure

IF

Control Mode = Constant Airflow

Setpoint Edit

Enter to select

Manual Control

Enter to select

Restore Factory Defaults:

Yes

Factory Defaults Enter to

select

IF

Control Mode = Constant Pressure

IF

Control Mode = Constant Airflow

Manual Out: 50%

Flow: 0 CFM

Exit

Manual Control Enter to

select

Factory Defaults Enter to

select

Setpoint Edit Enter to

select

Constant Pressure Control

6