beautypg.com

Troubleshooting – refrigeration circuit – Greenheck MPX (472695) User Manual

Page 35

background image

Always have a completed Pre Start-Up Checklist, Unit Start-Up Checklist and Optional Accessories Checklist prior to
requesting parts or service information.

Symptom Possible Cause

Corrective Action

Suction line
is frosting

Insufficient evaporator airflow.

Check airflow, check filters, check drive for loose parts
or belts.

Malfunctioning or defective expansion
valve.

Check bulb of thermal expansion valve.

Frost on
evaporator
coil

Hot gas bypass valve not functioning
properly.

Check valve. If defective, replace.

Manual hot gas bypass valve closed.

Open valve.

Low load or airflow.

Increase airflow, check filters.

Troubleshooting – Refrigeration Circuit

35

Model MPX Make-Up Air Unit

®