Wiring schematics, Potentiometer control, Timed exhaust frost control – Greenheck MiniVent (459023) User Manual

Page 8

background image

Energy Recovery Ventilator

8

®

Potentiometer Control

L2

L1

B

A

BLACK

WHITE

BLACK

BLACK

L1

GROUND

L2

ENERGY WHEEL MOTOR

WHITE

BLACK

M1

MAIN UNIT POWER -115/208/230/60/1

(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)

SEE NOTE#2

MB

MA

BLOWER MOTOR A

BLOWER MOTOR B

SEE NOTE#2

Wiring Schematics

L2

115

R

208

230

T

A OR B

L2

L1

L1

MAIN UNIT INTERNAL JUNCTION BOX

REMOTE PANEL

24V SECONDARY

16

15

T1

TR

GROUND

TH

COM

NO

A1

T1

A2

B1

FIELD MOUNT

IN OUTDOOR

AIR DUCT

PURPLE

115/208/230V PRIMARY

FIELD TO CONNECT

TO TERMINAL DESIGNATED

WITH UNIT LINE VOLTAGE

CONNECT TERMINAL 15

FROM COMPONENT "T1"

WITH LINE VOLTAGE

BLACK

ORANGE

RED

VIOLET

YELLOW

SEE NOTE #3

Timed Exhaust Frost Control

Legend
MA Blower Motor A
MB Blower Motor B
M1 Energy Wheel Motor
M2 Exhaust Blower Motor
M3 Supply Blower Motor
T1

Frost Control Timer
Typical

Settings:

t1 (OFF) = 5 min.
t2 (ON) = 30 min.

TH

Thermostat; non-adjustable 5° setting.
Required to be mounted in outdoor air duct.

TR Transformer