beautypg.com

Troubleshooting – Greenheck MiniVent (459023) User Manual

Page 14

background image

Energy Recovery Ventilator

14

®

Symptom

Possible Cause

Corrective Action

Unit is NOT
operating

Electrical

Check fuses/circuit breakers, replace if needed. Check
for On/Off switches. Check for correct supply voltage.

Motor

Check motor horsepower is correct and not tripping
overloads.

Excessive noise

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or
bearing collars on shaft.

Bearings

Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.

Wheel out of balance

Clean, replace or rebalance.

Low airflow (cfm)

Fan speed too low

Check for correct rpms with catalog data.

Fan wheels are operating
backwards

Refer to Blower Wheel Rotation information on page 12.

Dirty filters or energy wheel

Replace filters and/or follow the cleaning procedures.

High static pressure

Incorrect fan-to-duct connections. Make sure dampers
open appropriately. Increase fan speed

High airflow (cfm)

Fan speed too high

Check for correct fan rpm.

Low static pressure

Make sure grilles, filters and access doors are installed.
Decrease fan speed.

Energy wheel does
NOT turn

Air seals too tight

Refer to Energy Recovery Wheel, Air Seals on page 12.

No power to wheel motor

Make sure wheel drive is plugged in/connected. Verify
power is available.

Wheel drive belt

Check for loose or broken belts. Replace belts; consult
factory.

Energy wheel runs
intermittently

Wheel motor overloads are
tripping due to rubbing between
wheel and air seals.

Recheck air seals, make sure they are not too tight. See
Energy Recovery Wheel, Air Seals on page 12.

Always provide the unit model and serial number when requesting parts or service information. Always check
motor amps and compare to nameplate rating.

Troubleshooting