X. program settings – Greenheck Melink IH3 Operations User Manual
Page 14

X. Program
Settings
Below is a list of program settings for Intelli‐Hood. Please reference the Program Settings
Explanation Manual for additional details.
#
Parameter
Default Value
Range of Values
Hood Controller Parameters
HCxx‐01
Hood Network Address
1
0 To 39
HCxx‐02
Name
HC‐x
Up to 20 Characters
HCxx‐03
Optic Sensor
Yes
Yes or No
HCxx‐04
Temp Channel 1
Hood
No, Hood, Auto Only, Supply, Space
HCxx‐05
Temp Channel 1 Span Max. (°F)
90
50F To 200F (Increments Of 5F)
HCxx‐06
Temp Channel 2
No
No, Hood, Auto Only, Supply, Space
HCxx‐07
Temp Channel 2 Span Max. (°F)
Match Channel 1
50F To 200F (Increments Of 5F), Match Channel 1
HCxx‐08
Temp Channel 3
No
No, Hood, Auto Only, Supply, Space
HCxx‐09
Temp Channel 3 Span Max. (°F)
Match Channel 1
50F To 200F (Increments Of 5F), Match Channel 1
HCxx‐10
Temp Channel 4
No
No, Hood, Auto Only, Supply, Space
HCxx‐11
Temp Channel 4 Span Max. (°F)
Match Channel 1
50F To 200F (Increments Of 5F), Match Channel 1
HCxx‐12
Temp Actual Channel 1
Measured Temp
User Inputs Actual Temperature 0 To 500F
HCxx‐13
Temp Actual Channel 2
Measured Temp
User Inputs Actual Temperature 0 To 500F
HCxx‐14
Temp Actual Channel 3
Measured Temp
User Inputs Actual Temperature 0 To 500F
HCxx‐15
Temp Actual Channel 4
Measured Temp
User Inputs Actual Temperature 0 To 500F
HCxx‐16
Temp Channel 1 Span Min. (°F)
75
50F to 90F (Increments of 1F)
HCxx‐17
Temp Channel 2 Span Min. (°F)
Match Channel 1
50F to 90F (Increments of 1F), Match Channel 1
HCxx‐18
Temp Channel 3 Span Min. (°F)
Match Channel 1
50F to 90F (Increments of 1F), Match Channel 1
HCxx‐19
Temp Channel 4 Span Min. (°F)
Match Channel 1
50F to 90F (Increments of 1F), Match Channel 1
HCxx‐20
Optic Smoke Density
Medium
Low, Medium, or High
Exhaust Hood Parameters
EHxx‐01
Primary Exhaust ID
1
1 to 39
EHxx‐02
Name
Hood x
Up To 20 Characters
EHxx‐03
Minimum Speed
50%
30% To 100%, Increments Of 5%
EHxx‐04
Maximum Speed
100%
30% To 100%, Increments Of 5%
EHxx‐05
Select Hood Controllers
None Selected
0 to 39
EHxx‐06
Temperature Sensor Node(s)
00‐1 to 39‐4
EHxx‐07
Optic Sensor Node(s)
00 to 39
EHxx‐08
Auto On Hood Temperature
Auto On 120F
Not Used, Auto On 70F ‐ 120F
EHxx‐09
Auto On Space Differential
Not Used
Not Used, Room Difference +1F ‐ +40F
EHxx‐10
Auto Off Hood Temp
Not Used
Not Used, Auto Off 65F ‐ 100F
EHxx‐11
Auto Off Space Differential
Not Used
Not Used, Room Difference +1F ‐ +20F
EHxx‐12
Auto On/Off Grouping
Yes
Yes Or No
EHxx‐13
Digital Inputs To Utilize
Select All
DI 1, DI 2, DI 3
EHxx‐14
Digital Outputs To Affect
Select All
Relay 1, Relay 2, 24VDC 1, 24VDC 2
EHxx‐15
Temperature Alarm Auto On
System
Not Used, System, 100F, 125F, 150F, 200F, 250F,
300F
EHxx‐16
Short Cycle Ratio
Not Used
Not Used, 20%, 30%, 40%, 50%, 60%, 70%, 80%
EHxx‐17
User Interface On/Off
TP1
None, Touchpad 1‐10, Aux Touchpad 0‐9
EHxx‐18
Exhaust CFM
1000
0 to 100,000
EHxx‐19
Groups
1
1‐10
EHxx‐20
Touchpad Display Node
1
1‐10
EHxx‐21
Optic Hang time
System
System, 5, 10, 15, 30, 45, 60, 120, 180, 300