Greenheck DG / DGX with Direct Spark (470652) User Manual

Page 3

background image

Direct Spark Ignition Make-Up Air

3

®

Clearance to Combustibles /
Service Clearances

Floor

Top

Sides

Ends

Insulated/
Units

0 inches

(0 mm)

0 inches

(0 mm)

0 inches

(0 mm)

0 inches

(0 mm)

Non Insulated
Units

0 inches

(0 mm)

6 inches

(152.4 mm)

6 inches

(152.4 mm)

6 inches

(152.4 mm)

Clearance to combustibles is defined as the minimum distance
required between the heater and adjacent combustible surfaces
to ensure the adjacent surface’s temperature does not exceed
90 degrees above the ambient temperature.

Recommended Minimum Service Clearances

Housing 32 and less

42 inches (1066.8 mm)

on the controls side of the unit

Housing 35 and higher

48 inches (1219.2 mm)

on the controls side of the unit

Clearances for component removal (such as evaporative cooler media)
may be greater than the service clearances listed.

Table of Contents

Installation
Clearance

to

Combustibles/Service

Clearances

. . . . 3

Indoor

Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Unit Arrangement DB / HZ / UB . . . . . . . . . . . . . . . . 4
Roof Mounted Unit — Arrangement DBC . . . . . . . 5-6
Optional Evaporative Cooler Module . . . . . . . . . . . . . 6
Electrical

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Direct

Gas

Piping

. . . . . . . . . . . . . . . . . . . . . . . . . . 8-9

Optional Evaporative Cooler Piping . . . . . . . . . . . 9-10
Optional

Water

Wizard™

. . . . . . . . . . . . . . . . . . . . . 11

Optional Direct Expansion (DX) Coil Piping . . . . 12-13
Optional Chilled Water Coil Piping . . . . . . . . . . . . . 13
Optional Building Pressure Control . . . . . . . . . . . . . 14
Optional Dirty Filter Switch . . . . . . . . . . . . . . . . . . . 14
Start-Up
Blower

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Direct

Gas

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-18

Optional Evaporative Cooling Recirculating . . . . . . 19
Optional

Water

Wizard™

. . . . . . . . . . . . . . . . . . 20-21

Operation
Optional

Water

Wizard™

. . . . . . . . . . . . . . . . . . . . . 21

Optional

VAV

Units

. . . . . . . . . . . . . . . . . . . . . . . . . . 22

Optional Recirculating Units . . . . . . . . . . . . . . . . . . 23
Electrical

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Troubleshooting
Blower

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Motor

Overamps

. . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Insufficient / Too Much Airflow . . . . . . . . . . . . . . . . 27
Excessive Noise or Vibration . . . . . . . . . . . . . . . . . . 28
Direct Gas Heater Does Not Operate . . . . . . . . 29-30
Optional

Evaporative

Cooling

. . . . . . . . . . . . . . . . . 31

Optional

Water

Wizard™

. . . . . . . . . . . . . . . . . . . . . 32

Maintenance
Routine

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-34

Fall

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Reference
Gas Train Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Control

Center

Layout

. . . . . . . . . . . . . . . . . . . . . . 37

Start-Up Check List . . . . . . . . . . . . . . . . . . . . . . . . . 38
Maintenance

Log

. . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Installation of Indoor Unit

1. Install Hangers

Install threaded hangers from ceiling supports. When
locating hangers, allow enough room to open access
panel(s). Two nuts must be used on the end of each
threaded hanger. Ceiling supports are supplied by
others.

2. Install Unit

Using sheet metal screws, attach the weatherhood/
thru-wall/filter section to the blower/burner section.
The flange on the weatherhood/thru-wall/filter section
should overlap the flange on the blower/burner section.

Raise the assembled unit into place.

Using two nuts per hanger, fasten the unit supports to
the hangers under the unit. Appropriate unit supports,
such as the optional hanging bracket kit or c-channel
and angle iron (supplied by others) should be used.

Using self-tapping screws, attach ductwork to unit.

In order to prevent the unit from swinging and to provide
a safe environment for service and maintenance,
additional measures must be taken to secure the unit in
all directions.

NOTE

Two nuts must be used on each end of each threaded
hanging rod for proper support.

NOTE

Good duct practices should be followed for all
ductwork. Ductwork should be installed in accordance
with SMACNA and AMCA guidelines, NFPA 96 and
any local codes. Reference the CAPS submittal for
duct sizes.

3. Seal Wall Opening

Apply sealant around
the perimeter of the
weatherhood to prevent
water penetration and
drafts into the building.

Sealant

Seal Wall Opening

Indoor Mounting

Ceiling Supports

Unit Supports

Hangers

Ductwork