Models 1rvt7 and 1rvt8 – Dayton 1RVT8 User Manual
Page 5
®
Dayton Installation, Operation, Maintenance and Parts Manual
Models 1RVT7 and 1RVT8
5
Chart 1.1 - Clearance to Combustibles in Inches (see Figure 1.1)
Certain applications (awnings, fabrics, plastics, sprinklers,
insulation) may require the heater to be mounted at a
distance in excess of the published clearances to
combustibles. Contact the factory.
Figure 1.1 - Clearance to Combustibles
Model No.
Mounting
Angle*
Sides
Back
Top
Below
End(s)
Front
1RVT7
34,000 [Natural Gas]
0°
14
N/A
13
46
22
N/A
30°
N/A
8
17
46
22
46
1RVT8
34,000 [LP Gas]
0°
14
N/A
13
46
22
N/A
30°
N/A
8
17
46
22
46
End
End
SIDE VIEW
Below
Side
Side
END VIEW
0° MOUNTING ANGLE
Top
(to ceiling)
Back
This side down
Below
Front
30˚
* Heaters mounted on an angle between 0° to 30° must maintain clearances posted for 0° or 30°; whichever is greater.
Important! If the heater is mounted beneath a non-
combustible surface an 8 in. minimum top clearance
must be maintained from the top of the heater to
prevent overheating the controls.
Top
(to ceiling)
END VIEW
30° MOUNTING ANGLE