beautypg.com

Warning, Models 1rvt7 and 1rvt8, Gas supply – Dayton 1RVT8 User Manual

Page 13

background image

®

Dayton Installation, Operation, Maintenance and Parts Manual

Models 1RVT7 and 1RVT8

13

Gas Supply

WARNING

!

Improperly connected gas lines may result in fire,
explosion, poisonous fumes, toxic gases, asphyxiation
and death. Connect gas lines in accordance to
national, state, provincial and local codes.

Chart 2.2 - Manifold Pressure

Type of

Required Manifold

Minimum Inlet

Maximum Inlet

Gas

Pressure

Pressure

Pressure

Pressure Equivalents: 1 in. W.C.P. equals .058 oz./sq. in. equals 2.49 Mbar.

Note: Check manifold pressure at the tap on the ball shutoff valve. Readings will be above atmospheric

pressure during operation.

The gas supply to the infra-red heater must be
connected and tested in accordance with national, state,
provincial and local codes along with the guidelines in
this manual. Refer to the latest edition of the ANSI
Z223.1 (NFPA 54) Standard.

Natural

5.0 in. W.C.P.

6.0 in. W.C.P.

14.0 in. W.C.P.

Liquefied Petroleum

10.0 in. W.C.P.

11.0 in. W.C.P.

14.0 in. W.C.P.

Important! Before connecting the gas supply to the
infra-red heater(s):

• Check for conditions such as drafts or other variables

which might cause excessive movement of the unit
and cause damage to the gas connection. Ensure that
the unit is securely mounted and connect the gas with
an approved connection device suitable for the
environment of use.

• Check that the gas piping and service has the capacity

to handle the load of all heaters being installed, as well
as any other gas appliances being connected to the
supply line.

• Check that the main gas supply line is of proper

diameter to supply the required fuel pressures.

• If utilizing used pipe, verify that its condition is clean

and comparable to a new pipe. Test all gas supply lines
in accordance with local codes.

• Test and confirm that inlet pressures are correct. Refer

to the rating plate for required minimum and
maximum pressures (see Chart 2.2). The gas supply
pipe must be of sufficient size to provide the required
capacity and inlet pressure to the heater (if necessary,
consult the local gas company).

• For test pressures in excess of 1/2 psig (3.5 kPa), the

heater and ball shutoff valve must be disconnected
from the gas supply piping system during any pressure
testing of the system.

• For test pressures equal to or less than 1/2 psig (3.5

kPa), the heater must be isolated from the gas supply
piping system by closing it’s individual manual shutoff
valve during any pressure testing of the gas supply
piping system.

This manual is related to the following products: