Specifications – GAI-Tronics 12598-004 Redundant 48 V DC Module User Manual
Page 4
Pub. 42004-468A
Model 12598-004 Redundant 48 V DC Module
Page: 4 of 4
f:\standard ioms - current release\42004 instr. manuals\42004-468a.doc
10/12
Specifications
Electrical
Power requirements ............................................................................................................ 48 V dc nominal
Current handling capacity ................................................................................... 2.5A maximum @ 48 V dc
Voltage drop from input(s) to output .................................................... Approximately 0.6 V dc to 0.9 V dc
Number of inputs .................................................................................................................................... Two
Number of outputs ................................................................................................................................... One
Number of fault outputs ............................................................................................... Four (Two per input)
Fault output type .......................................................................................................... Form “C” dry contact
Fault output contact rating .................................................................................... 1 A maximum @ 30 V dc
Terminations
Type ......................................................................................................... Modular (plug-in) terminal blocks
Minimum conductor size .......................................................................................... No. 28 AWG (0.5 mm
2
)
Maximum conductor size .......................................................................................... No. 12 AWG (3.0 mm
2
)
Mechanical
Module dimensions ........................................ 4.00 L
4.00 W 1.50 H inches (101.6 101.6 38.1 mm)
Module weight .................................................................................................................. 0.32 lbs. (0.14 kg)
Environmental
Temperature range – 100% load (operating ambient) ........................................... 32
to 77 F (0 to 25 C)
Temperature range – 50% load (operating ambient)........................................... 32
to 115 F (0 to 46 C)
Temperature range – 25% load (operating ambient)........................................... 32
to 140 F (0 to 60 C)
Temperature range (storage) ............................................................................... 32
to 140 F (0 to 60 C)
Humidity .......................................................................................... 85% non-condensing relative humidity
- XTA0003A Radio Cable 12564-002 Party Line Knob Kit (EuroPage) XTI0001A-G3 Radio Cable 10959-207 and 10959-208 Rack-mount Audio Messenger Interface 10959-201 and 10959-203 Wall-mount Audio Messenger Interface 10959-903 Wall-Mount Audio Messenger Interface (AMI) XGM003A Gooseneck Microphone Kit 12515-007, 12515-008, 12515-009 Pressbar Handset with Hytrel Cord Replacement Kit