Specifications – GAI-Tronics 12598-001 Redundant 12 V DC Module User Manual
Page 5
Pub. 42004-400A
Model 12598-001 Redundant 12V DC Module
Page: 5 of 5
f:\standard ioms - current release\42004 instr. manuals\42004-400a.doc
07/07
Specifications
Electrical
Power requirements ................................................................................... 10–14 V dc (12 V dc nominal)
Current handling capacity................................................................................ 10 A maximum @ 12 V dc
Voltage drop from input(s) to output.................................................. Approximately 0.6 V dc to 0.9 V dc
Number of inputs..................................................................................................................................... 2
Number of outputs................................................................................................................................... 1
Number of fault outputs............................................................................................ Four (Two per input)
Fault output type ..................................................................................................... Form “C” dry contact
Fault output contact rating ................................................................................. 1 A maximum @ 30 V dc
Terminations
Type..................................................................................................... Modular (plug-in) terminal blocks
Minimum conductor size ...................................................................................... No. 28 AWG (0.5 mm
2
)
Maximum conductor size...................................................................................... No. 12 AWG (3.0 mm
2
)
Mechanical
Module dimensions ...................................... 4.00 L
× 4.00 W × 1.50 H inches (101.6 × 101.6 × 38.1 mm)
Module weight ............................................................................................................. 0.32 lbs. (0.14 kg)
Environmental
Temperature range – 100% load (operating ambient) ......................................... 32
° to 77° F (0° to 25° C)
Temperature range – 50% load (operating ambient) ......................................... 32
° to 115° F (0° to 46° C)
Temperature range – 25% load (operating ambient) ......................................... 32
° to 140° F (0° to 60° C)
Temperature range (storage) ............................................................................ 32
° to 140° F (0° to 60° C)
Humidity....................................................................................... 85% non-condensing relative humidity