Status codes in the event of a charging fault
Number
Cause
(31)
Time exceed in I1 phase
(32)
Time exceed in U1 phase
(34)
Ah exceed
(35)
Time exceed in I2 phase
(36)
Set voltage not reached in I2 phase (format characteristic only)
(37)
Problem with RI charge
(38)
Set charging time cannot be reached
Status codes in the event of a fault in the primary circuit
Number
Cause
(500)
Module 1 (top) temperature sensor faulty
(501)
Module 2 (bottom) temperature sensor faulty
(502)
PCB temperature sensor faulty
(503)
Primary overtemperature
(504)
Fan jammed/faulty
(505)
Intermediate circuit over/undervoltage
(506)
Intermediate circuit imbalance
(507)
Primary supply voltage outside the tolerance
(508)
Power failure
(509)
Wrong device configuration
(510)
Primary EEPROM faulty
Status codes in the event of a fault in the secondary circuit
Number
Cause
(520)
Secondary temperature sensor faulty
(521)
Secondary overtemperature
(522)
Output fuse faulty
(523)
Secondary supply voltage outside the tolerance
(524)
Secondary reference voltage outside the tolerance
(525)
Current offset
(526)
Current offset outside the tolerance
(527)
Power module overcurrent (primary)
(529)
No secondary communication
(530)
No primary communication
(531)
Secondary EEPROM faulty
(532)
μC fault
Status codes in the event of a fault in the controller
Number
Cause
(540)
CFM missing/faulty
(541)
No secondary communication
(542)
Secondary initialisation failed
(543)
Program/memory fault in characteristic control
(544)
Program/memory fault in characteristic control