Flowserve Guardian Sealless Metallic User Manual
Page 21

GUARDIAN USER INSTRUCTIONS ENGLISH 71569212 08-11
Page 21 of 68
flowserve.com
Refer to section 3.4 for performance and operating 
limits. 
 
4.6.2.1 
Guardian self-priming pumps
The suction piping must be as short as possible and be 
as close to the diameter of the suction nozzle as is 
practical. The pump works by removing the air 
contained in the suction piping. Once removed, it 
operates exactly the same as a flooded suction 
standard pump. Longer and larger suction pipes have a 
greater volume of air that has to be removed, resulting 
in longer priming time. The suction piping and seal 
chamber must be airtight to allow priming to occur. 
When possible, it is recommended that suction piping 
be sloped slightly towards the casing to ensure no fluid 
is lost down the suction line during priming. 
 
4.6.3 
Discharge piping
Install a valve in the discharge line. This valve is 
required for regulating flow and/or to isolate the pump 
for inspection and maintenance. 
When fluid velocity in the pipe is high,
for example, 3 m/s (10 ft/s) or higher, a rapidly 
closing discharge valve can cause a damaging 
pressure surge. A dampening arrangement should 
be provided in the piping. 
 
4.6.3.1 
Guardian self-priming pumps
During the priming cycle, air from the suction piping is 
evacuated into the discharge piping. There must be 
a way for this air to vent. If air is not able to freely 
vent out the discharge pipe, it is typically 
recommended to install an air bleed line. The air 
bleed line is typically connected from the discharge 
pipe to the sump. Care must be taken to prevent air 
from re-entering suction pipe. 
 
4.6.4 
Allowable nozzle loads
Flowserve chemical process pumps meet or exceed 
the allowable nozzle loads given by ANSI/HI 9.6.2. 
The following paragraphs describe how to calculate 
the allowable loads for each pump type and how to 
determine if the applied loads are acceptable. The 
configuration covered is for ASME B73.3 pumps, 
including the Guardian G & H series. 
 
4.6.4.1 
Guardian G & H series pumps (ASME 
B73.3) 
The following steps are based upon ANSI/HI 9.6.2. 
All information necessary to complete the evaluation 
is given below. For complete details please review 
the standard. 
a) Determine the appropriate casing “Material Group 
No.” from figure 3-8.
b) Find the “Casing material correction factor” in
Figure 4-9 based upon the “Material Group No.” 
and operating temperature. Interpolation may be 
used to determine the correction factor for a 
specific temperature. 
c) Find the “Baseplate correction factor” in Figure
4-10. The correction factor depends upon how 
the baseplate is to be installed. 
d) Locate the pump model being evaluated in Figure
4-14 and multiply each load rating by the casing 
correction factor. Record the “adjusted Figure 4-14 
loads”. 
e) Locate the pump model being evaluated in
Figures 4-15 and 4-16 and multiply each load 
rating by the baseplate correction factor. Record 
the adjusted Figure 4-15 and 4-16 loads. 
f)
Compare the “adjusted Figure 4-14 loads” to the 
values shown in figure 4-13. The lower of these 
two values should be used as the adjusted figure 
4-13 values. (The HI standard also asks that figure 
4-13 loads be reduced if figure 4-15 or 4-16 values 
are lower. Flowserve does not follow this step.) 
g) Calculate the applied loads at the casing flanges
according to the coordinate system found in 
figure 4-11. The 12 forces and moments possible 
are Fxs, Fys, Fzs, Mxs, Mys, Mzs, Fxd, Fyd, Fzd, 
Mxd, Myd and Mzd. For example, Fxd 
designates Force in the “x” direction on the 
discharge flange. Mys designates the Moment 
about the “y”-axis on the suction flange. 
h) Figure 4-12 gives the acceptance criteria
equations. For long coupled pumps, equation 
sets 1 through 5 must be satisfied. For close 
coupled pumps, only equation sets 1 and 2 must 
be satisfied. 
i)
Equation set 1. Each applied load is divided by 
the corresponding adjusted figure 4-13 value. 
The absolute value of each ratio must be less 
than or equal to one. 
j)
Equation set 2. The summation of the absolute 
values of each ratio must be less than or equal to 
two. The ratios are the applied load divided by 
the adjusted figure 4-14 values. 
k) Equation sets 3 and 4. These equations are
checking for coupling misalignment due to nozzle 
loading in each axis. Each applied load is divided 
by the corresponding adjusted load from figure 4-15 
and 4-16. The result of each equation must be 
between one and negative one. 
l)
Equation set 5. This equation calculates the total 
shaft movement from the results of equations 3 
and 4. The result must be less than or equal to 
one. 
