beautypg.com

2 specifications, 1 electrical, 2 environmental – Contemporary Control Systems BASrouter Installation Guide (Firmware 2.x) User Manual

Page 5: 3 mounting, 4 functional, 5 regulatory compliance, 6 electromagnetic compatibility, 3 mounting 2.4 functional

background image

TD071200-0IK

5

2 Specifications

2.1 Electrical

INPUT

DC

AC

Voltage (±10%):

24 V

24 V

Power:

2 W

4 VA

Frequency:

N/A

47–63 Hz

2.2 Environmental

Operating temperature:

0°C to 60°C

Storage temperature:

–40°C to +85°C

Relative humidity:

10–95%, non-condensing

2.3 Mounting

2.4 Functional

Ethernet

MS/TP

Physical Layer:

10BASE-T

EIA-485

100BASE-TX

Cable length limit:

100 m

1200 m (for AWG 18)

MS/TP Baud rate (bps):

9600, 19200, 38400, 76800

MS/TP node limit:

254 devices total,

31 full-load devices per segment

MS/TP LED:

flashing green = receive valid activity

Ethernet LED:

green = 100 Mbps

yellow = 10 Mbps

flashing = activity

2.5 Regulatory Compliance

CE Mark; RoHS; CFR47, Part 15 Class A

2.6 Electromagnetic Compatibility

Each unit complies with Class A radiated and conducted emissions
as defined by EN55022 and CFR 47, Part 15. This equipment is
intended for use in non-residential areas.

Warning This is a Class A product as defined in EN55022. In a domestic
environment this product may cause radio interference in which case the
user may be required to take adequate measures.

TS-35 DIN-rail

(Class 2 Circuits Only)