Operation – Delta DT3 User Manual

Page 2

background image

2

V: Voltage Pulse Output, 12V ±10%

C: DC Current Output 4 ~ 20 m A
L: Linear Voltage Ouptut 0 ~ 10 VDC

EVENT inputs/ CT function (optional) 1

0: None, 1: Event Input3, 2: RS-485 Communication

EVENT inputs/ CT function (optional) 2

0: None, 1: Event Input2, 2: CT measure input2, 3: Retransmission Output

EVENT inputs/ CT function (optional) 3

0: None, 1: Event Input1, 2: CT measure input1, 3: Remote Setpoint input


 

Specifications

Input Voltage

AC 80 ~ 260 V, 50/60Hz; DC24 VDC ±10%

Power Consumption

5VA max.

Display Method

LCD display. Process value (PV): Yellow color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100

Sensor Type

Analog input: 0 ~ 5 V, 0 ~ 10 V, 0 ~ 20 m A, 4 ~ 20 mA, 0 ~ 50 mV

Control Mode

PID, PID program control (Ramp/Soak control), FUZZY, Self-tuning, Manual and On/FF

Relay output: Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 12V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 500Ω)

Control Output

Analog voltage output: 0 ~ 10V

Warning Output Type

Relay output: Max. load 250VAC, 3A resistive load

Display Accuracy

0 or 1 digit to the right of the decimal point (selectable)

Sampling Rate

Analog input: 0.1 sec/ per scan; Thermocouple or Platinum RTD: 0.1 sec/per scan

Vibration Resistance

10 to 55Hz, 10m/s

2

for 10min, each in X, Y and Z directions

Shock Resistance

Max. 300m/ s

2

, 3 times in each 3 axes, 6 directions

Ambient Temperature

0°C ~ +50°C

Storage Temperature

-20°C ~ +65°C

Altitude

Max. 2000m

Relative Humidity

35% ~ 80% RH(non-condensing)


 

Operation

™

There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation

mode. Press the

key to switch to regulation mode. If the

key is pressed for more than 3 seconds, controller will switch to the

initial setting mode. Pressing the

key while in the regulation mode or initial setting mode, forces the controller to return to the

operation mode..

™

PV/SV: Sets the temperature set point and displays the temperature process value. Use

keys to set the temperature set

point.

™

Setting method: While in any function mode, press the

key to select the desired function and use

keys to change

settings. Press

key to save the changes.

™

The flow chart below shows how to switch the settings and internal functions:

Regulation Mode

Operation Mode

Initial Setting Mode

Press key less than 3 sec

Press key

Press key more than 3 sec

Press key

Operation

Mode

Parameter Setting:

Display

Description

Factory Setting

Use

to set temperature set point, use

to switch between the display parameter

RUN/STOP: Control setting RUN or STOP

RUN

PATTERN: Start pattern setting (set control mode to PROG mode)

0

STEP: Start step setting (set control mode to PROG mode)

0

SELECT POINT: Decimal point setting (0: integral ; 1: one decimal point)

1

LOCK: Setting lock mode (LOCK1: all; LOCK2: onlySV and F1/F2 key is allowed)

OFF

ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)

4.0