Delta DT3 User Manual

Page 19

background image

19

1103H

Reverse Output

Bit1: output 2, Bit0: output 1

1104H

Slope of Temperature Increase

Unit: 0.1 /

min or 0.1℃/sec (refer to CommunicationAddress 1124H)

1105H

Remote Input Type Selection

0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V

1106H

AT Control

0: AT(Auto-tune), 1: ST(Self-tune)

1107H

Remote Input Reverse Setting

0: forward, 1: reverse

1108H

Alarm 1 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

1109H

Alarm 2 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

110AH

Alarm 3 Function Selection

Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable

110BH

Alarm 1 Output Delay Time

Unit: second. Setting range: 0~100sec

110CH

Alarm 2 Output Delay Time

Unit: second. Setting range: 0~100sec

110DH

Alarm 3 Output Delay Time

Unit: second. Setting range: 0~100sec

110EH

Upper Limit of Control Output 1

Range: lower limit of control output ~100%, unit is 0.1%

110FH

Lower Limit of Control Output 1

Range: 0~upper limit of control output, unit is 0.1%

1110H

Upper Limit of Control Output 2

Range: lower limit of control output~100%, unit is 0.1%

1111H

Lower Limit of Control Output 2

Range: 0~upper limit of control output, unit is 0.1%

1112H Programmable

Waiting

Temeprature

Setting range: 0~1000(100.0 )

1113H

Programmable Waiting Time

Unit: min. Setting range: 0~900

1114H

Programmable Slope Increase

Unit: 0.1℃/min or 0.1℃/sec--- (refer to Communication Address 1124H) Setting
range: 0~1000

1115H Testing

Mode

1116H

Adjust Upper Limit of Analog
Linear Output 1

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

1117H

Adjust Lower Limit of Analog
Linear Output 1

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

1118H

Adjust Upper Limit of Analog
Linear Output 2

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

1119H

Adjust Lower Limit of Analog
Linear Output 2

Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV

111AH

Adjust Retransmission Upper
Limit

Adjust current: 1scale=1μA

111BH

Adjust Retransmission Lower
Limit

Adjust current: 1scale=1μA

111CH

Event 1 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode

111DH

Event 2 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode

111EH

Event 3 Selection

0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode

111FH

PV Control Mode Selection

0: PID, 1: ON/OFF, 2: Manual control, 3: Fuzzy

1120H

SV Control Mode Selection

0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input

1121H

Adjust Remote Compensation

Setting range: -999~999

1122H

Adjust Remote Gain

Setting range: -999~999

1123H

Positive/Negative Selection for
Remote

0: Positive, 1: Negative

1124H

Switch Slope Time Unit

0: min, 1: sec

1125H

Cold Junction Compensation

0: ON, 1: OFF

1126H

Reserve the Programmable
Running Status when Power OFF

0: None, 1: Running status is saved and will continue by the previous status when
power ON.

1127H

Fuzzy Gain

Setting range: 1~10

1128H

Fuzzy Dead Band

Setting range: 0.0~PB

1129H

Save Programmable Settings
into Memory

0:None, 1: Saves the programmable settings into memory

1182H

CT1 Read Value

Unit: 0.1A

1183H

CT2 Read Value

Unit: 0.1A

1. Address and Content of Bit Register: First bit of reading will put into LSB. Write data= FF00H for bit set, 0000H for bit clear.

0810H

Read AT LED status

0: OFF(default), 1: ON

0811H

Temperature unit display

0: , 1: /

linear input (default)