1103H
Reverse Output
Bit1: output 2, Bit0: output 1
1104H
Slope of Temperature Increase
Unit: 0.1 /
℃
min or 0.1℃/sec (refer to CommunicationAddress 1124H)
1105H
Remote Input Type Selection
0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V
1106H
AT Control
0: AT(Auto-tune), 1: ST(Self-tune)
1107H
Remote Input Reverse Setting
0: forward, 1: reverse
1108H
Alarm 1 Function Selection
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
1109H
Alarm 2 Function Selection
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
110AH
Alarm 3 Function Selection
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
110BH
Alarm 1 Output Delay Time
Unit: second. Setting range: 0~100sec
110CH
Alarm 2 Output Delay Time
Unit: second. Setting range: 0~100sec
110DH
Alarm 3 Output Delay Time
Unit: second. Setting range: 0~100sec
110EH
Upper Limit of Control Output 1
Range: lower limit of control output ~100%, unit is 0.1%
110FH
Lower Limit of Control Output 1
Range: 0~upper limit of control output, unit is 0.1%
1110H
Upper Limit of Control Output 2
Range: lower limit of control output~100%, unit is 0.1%
1111H
Lower Limit of Control Output 2
Range: 0~upper limit of control output, unit is 0.1%
1112H Programmable
Waiting
Temeprature
Setting range: 0~1000(100.0 )
℃
1113H
Programmable Waiting Time
Unit: min. Setting range: 0~900
1114H
Programmable Slope Increase
Unit: 0.1℃/min or 0.1℃/sec--- (refer to Communication Address 1124H) Setting
range: 0~1000
1115H Testing
Mode
1116H
Adjust Upper Limit of Analog
Linear Output 1
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1117H
Adjust Lower Limit of Analog
Linear Output 1
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1118H
Adjust Upper Limit of Analog
Linear Output 2
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1119H
Adjust Lower Limit of Analog
Linear Output 2
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
111AH
Adjust Retransmission Upper
Limit
Adjust current: 1scale=1μA
111BH
Adjust Retransmission Lower
Limit
Adjust current: 1scale=1μA
111CH
Event 1 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
111DH
Event 2 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
111EH
Event 3 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
111FH
PV Control Mode Selection
0: PID, 1: ON/OFF, 2: Manual control, 3: Fuzzy
1120H
SV Control Mode Selection
0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input
1121H
Adjust Remote Compensation
Setting range: -999~999
1122H
Adjust Remote Gain
Setting range: -999~999
1123H
Positive/Negative Selection for
Remote
0: Positive, 1: Negative
1124H
Switch Slope Time Unit
0: min, 1: sec
1125H
Cold Junction Compensation
0: ON, 1: OFF
1126H
Reserve the Programmable
Running Status when Power OFF
0: None, 1: Running status is saved and will continue by the previous status when
power ON.
1127H
Fuzzy Gain
Setting range: 1~10
1128H
Fuzzy Dead Band
Setting range: 0.0~PB
1129H
Save Programmable Settings
into Memory
0:None, 1: Saves the programmable settings into memory
1182H
CT1 Read Value
Unit: 0.1A
1183H
CT2 Read Value
Unit: 0.1A
1. Address and Content of Bit Register: First bit of reading will put into LSB. Write data= FF00H for bit set, 0000H for bit clear.
0810H
Read AT LED status
0: OFF(default), 1: ON
0811H
Temperature unit display
0: , 1: /
℉
℃
linear input (default)