Delta DT3 User Manual

Page 18

background image

18

1006H

Heating/Cooling control selection Refer to Ouputput Mode Selection

1007H

1st group of Heating/Cooling
control cycle

1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second

1008H

2nd group of Heating/Cooling
control cycle

1~990, unit is 0.1 second. When the output setting = realy, the minimum control
cycle is 5 second 1~990

1009H

PB Proportional band

0.1 ~ 999.9

100AH

Ti Integral time

0~9,999

100BH

Td Derivative time

0~9,999

100CH

Integration default

0 ~ 100%, unit is 0.1%

100DH

Proportional control offset error
value, when Ti=0

0 ~ 100%, unit is 0.1%

100EH

The setting of COEF when Dual
Loop output control are used

0.01 ~99.99, unit is 0.01

100FH

The setting of Dead Band when
Dual Loop output control are
used

-999 ~ 9,999

1010H

Hysteresis setting value of the
1st output group

0~9,999

1011H

Hysteresis setting value of the
2nd output group

0~9,999

1012H

Output value read and write of
Output 1

Unit is 0.1%, write operation is valid under manual tuning mode only.

1013H

Output value read and write of
Output 2

Unit is 0.1%, write operation is valid under manual tuning mode only.

1016H

Temperature regulation value

-99.9 ~ +99.9. Unit is 0.1

1017H

Analog decimal setting

0 ~ 3

101CH

PID parameter selection

0~5/AUTO

101DH

SV value corresponded to PID
value

Only valid within available range, unit: 0.1 scale

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

102AH

Read LED Status

b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT

102BH

Read Pushbutton Status

b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key

102CH

Setting lock status

102FH

Software version

V1.00 indicates 0x100

1030H

Start pattern number

0 ~ 15

1200H~13FFH

Pattern 0~15 temperature set
point setting (Even number)
Pattern 0~15 execution time
setting (Odd number)

-999 ~ 9999
Time: 0 ~ 900(1 minute per scale)

1400H~140FH

Actual number of step setting
inside the corresponding pattern

0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N

1410H~141FH

Cycle number for repeating the
execution of the correspond
pattern

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times

1420H~142FH

Link pattern number setting of
the correspond pattern

0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern

Address

Content

Definition

1100H Adjust

Temperature

Gain

1101H

Temperature Filter Range

Range of temperature filter: 10~1000, unit: 0.01 ℃, default: 100(1.0℃)

1102H

Temperature Filter Factor

Setting range: 0~50, default: 8