Rs-485 communication – Delta DT3 User Manual

Page 17

background image

17

17

When HOLD status happens to PID program control, alarm output is ON.

18

When STOP status happens to PID program control, alarm output is ON.

19

When END status happens to PID program control, alarm output is ON.

¾

To set Alarm Mode: Use the parameters

,

,

in 【Initial Setting Mode】 to select the alarm mode. There are

in total of 19 different modes (as listed in the table above).

¾

To set Deviation Upper Limit of Alarm: Use the parameters

,

,

in 【Operation Mode】to set the deviation

upper limit.

¾

To set Deviation Lower Limit of Alarm: Use the parameters

,

,

in 【Operation Mode】 to set the deviation

lower limit.

¾

To set Alarm Delay Time(Unit: seconds): Use the parameters

,

,

in 【Initial Setting Mode】 to set the alarm

delay time.

¾

To set Reverse Alarm: Use the parameters

,

,

in【Initial Setting Mode】 to set the digit Y of value xxYx

(When Y=0: reverse, Y=1: forward)

¾

To set Alarm 3: Alarm 3 function is available when an output board is connected to Output 2. Use the parameter

in【Initial

Setting Mode】, press the key ▲ or ▼ to select for the following control output items: H1H2, C1H2… H1A2(H defines heating, C
defines cooling, 1 indicates Output1, 2 indicates Output2 , A indicates Alarm3).

¾

Select x1A2( set x to H or C) to operates Alarm3. To set Standby Alarm: Use the parameters

,

,

in 【Initial

Setting Mode】 to set the digit Y of value xxxY (When Y=0: normal opeartion, Y=1: standby).

¾

To set Hold Alarm: Use the parameters

,

,

in【Initial Setting Mode】 to set the digit Y of value xYxx ( When

Y=0: normal operation, Y=1: Hold).

¾

To set Peak Alarm Signal: Use the parameters

,

,

in【Initial Setting Mode】 to set the digit Y of value Yxxx

(when Y=0: normal operation, Y=1: peak signal).

Note: Refer to the table


¾

PV Color Change Function: This controller provides PV color change function. The PV display color will be changed if the selected

alarm energized. Use the parameter

(PV color) in 【Initial Setting Mode】 to select the alarm, selectable items are

,

,

,

and

.


 

RS-485 Communication

1.

Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps

2.

Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2

3.

Communication protocol: Modbus (ASCII or RTU)

4.

Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits

data (Max.16 bits). 05H to write 1 (one) bit into register.

5.

Address and Content of Data Register:

Address

Content

Definition

Measuring unit is 0.1, updated one time in 0.1 second
The following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error

1000H

Present value (PV)

8007H : Memory read/write error

1001H

Set point (SV)

Unit is 0.1, oC or oF

1002H

Upper-limit of temperature range

The data content should not be higher than the temperature range

1003H

Lower-limit of temperature range

The data content should not be lower than the temperature range

1004H

Input temperature sensor type

Please refer to the contents of the “Temperature Sensor Type and Temperature
Range” for detail

1005H

Control method

0: PID, 1: ON/OFF, 2: manual tuning, 3: FUZZY

Bit3

Bit2

Bit1

Bit0

Peak Alarm

Hold Alarm

Reverse Alarm Standby Alarm