Belshaw Adamatic TG50 Thermoglaze User Manual
Page 16
![background image](https://www.manualsdir.com/files/775247/content/doc016.png)
Belshaw Bros., Inc.
• www.belshaw.com • Phone 206-322-5474 • Fax 206-322-5425
10 MN-1720
Thermoglaze
50
TG-50 Parameter Settings
Tables 1, 2 and 3 below list of the temperature controller default settings and the Belshaw Factory
settings. When installing a new controller 3 of the default setting must be changed to the Belshaw
Factory settings.
• Push and hold the scroll key
for 3 seconds, this will take you to the “SEt” menu.
• Push the scroll key
once to access the “LocK” parameter.
• Push the Up
or down
arrow keys to change “LocK” to “nonE”.
• Push the scroll key
to page through the settings and the Up
or down
arrow keys to
change the settings listed in the Belshaw “Factory” column. (see tables 1, 2 and 3)
When finished setting parameters.
• Continue pushing the scroll key
until you are back to “LocK”.
• Push the Up
or down
arrow keys to set “LocK” to “uSEr”.
• Push the reset key
to return normal operation.
Default Settings:
In the event that parameters have been modified without recording the modifications, change each
parameter to match those listed in Tables 1, 2 and 3 listed below (controller parameter default settings).
Then adjust SP1H, PB, OUT2 and the LocK parameters as listed in Belshaw “Factory” below. Then set
SP1 to 420ºF.