5.3.1 CouplerState ( BK52x0, ILX-52x)

Note: This Status-Variable is Bit-Encoded

Error Code

(hex)

Description

Troubleshooting

0x00

No Error

None

0x01

IO Error

Data exchange between coupler and ter-
minals has faulted. Check the IO error
LEDs at the coupler, see error code in
coupler manual

0x02

Coupler configuration error, devices non-
volatile parameters are not valid

Set Manufacturers Setting e.g. with
KS2000 or via register communication and
reset coupler.

0x08

Diagnoses of analogue terminals, this
feature has first to be activated via
KS200 or register communication

Read the terminal diagnoses via explicit
messages or via the Bit-Strobe Connec-
tion. The Bit is resetted after reading of the
diagnosis data

0x80

Fieldbus Error / Idle Mode

Check Communication Parameter of the IO
Connections. Check if the Device is in the
Idle mode. The bit is reseted if the device
receives valid IO data