3 master-functionality, 4 slave-functionality – BECKHOFF FC520x User Manual
Page 42
Eiserstraße 5 / D-33415 Verl / Telefon 05246/963-0 / Telefax 05246/963-149
FC520x / CX1500-x520
41
BECKHOFF FC520x / CX1500-x520
5.1.3 Master-Functionality
LED
Description
Troubleshooting
Green Flashing
Master in online, has finished the
Duplicate MacId Check
None
Green on
Master is online and communicates
with its configured Slaves
None
Red Flashing
Master has lost communication with
one of the configured Slaves
Inspect the devices, verify connections,
check cabling
Red on
DeviceNet Bus OFF, DeviceNet
Voltage Error, Master failed Dupli-
cate MacId Check
Check Baudrate and cabling, Master is
may not able to set up his Duplicate Mac Id
messages, Check DeviceNet Voltage (24
Volt) at DeviceNet Connector
5.1.4 Slave-Functionality
LED
Description
Troubleshooting
Green Flashing
Slave port has finished the Duplicate
MacId Check (Network OK), Slave
Port is not communicating with its
Master
None
Green on
Slave port is online and communi-
cates with its Master
None
Red Flashing
Slave port has lost communication
with its Master, Timeout of Slave-
Port
Inspect the Master device, verify connec-
tions, check cabling
Red on
DeviceNet Bus OFF, DeviceNet
Voltage Error, Slave port failed Du-
plicate MacId Check
Check Baudrate and cabling, Slave Port is
may not able to set up his Duplicate Mac Id
messages, Check DeviceNet Voltage (24
Volt) at DeviceNet Connector