4 diagnostics, 1 diagnostic leds – BECKHOFF EL6930 User Manual
Page 53

Operation
EL6930
51
4.4 Diagnostics
4.4.1
Diagnostic LEDs
The LEDs Diag 1 to Diag 4 display diagnostic information for the EL6930.
4.4.1.1
Diag 1 LED (green)
The Diag 1 LED is currently always on when a project is loaded into the terminal.
Display
Meaning
lit
A project is stored in the terminal.
4.4.1.2
Diag 2 LED (red)
The Diag 2 LED indicates internal process variable errors (in preparation).
Display
Meaning
in preparation
4.4.1.3
Diag 3 LED (red)
The Diag 3 LED provides further details for the Diag 4 LED (see below).
4.4.1.4
Diag 4 LED (red) if Diag 3 LED (red) is lit
If the Diag 3 LED is lit, the Diag 4 LED indicates internal terminal errors.
Diag 3 LED
Diag 4 LED
Source of error
lit
flashing
µC1
lit
off
µC2
Note
Returning the terminal
These errors lead to the shutdown of the terminal (global fault). The terminal must be
checked by Beckhoff Automation GmbH & Co. KG.