BECKHOFF EL6930 User Manual
Page 25

Operation
EL6930
23
4.1.5
Tested EL2904 devices
The following list contains devices that were tested together with the EL2904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out
in a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.
Manufacturer
Type
Comment
Beckhoff
AX5801
TwinSAFE Drive option card: safe restart lock
Beckhoff
AX2000 Option AS
safe restart lock
Siemens
SIRIUS Serie S00
3RT1016-1BB42
Contactor
Telemecanique LP1K09
Contactor
The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.
Note
Recommended protective circuits
We recommend R/C or diode-based protective circuits for these devices.
Varistor-based protective circuits should not be used.
4.1.6
Tested EL1904 devices
The following list contains devices that were tested together with the EL1904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out
in a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.
Manufacturer Type
Comment
SICK
C4000
Safety light curtain
SICK
S3000
Safety laser scanner
Wenglor
SG2-14ISO45C1
Safety light grids
Leuze
lumiflex ROBUST 42/43/44
Safety light barriers
Schmersal
BNS250-11ZG
Safety switch
ifm
GM701S
Inductive safety sensor
The tests were carried out as function tests only. The information provided in the respective manufacturer