3 technical data – BECKHOFF EL6930 User Manual
Page 16

Product description
14
EL6930
3.3 Technical data
Product designation
EL6930
Number of inputs
0
Number of outputs
0
Status display
4 diagnostic LEDs
Minimum cycle time
approx. 500 µs
Error reaction time
≤
watchdog times
Watchdog time
min. 1 ms, max. 60,000 ms
Input process image
Dynamic according to the TwinSAFE configuration in
the TwinCAT System Manager
Output process image
Dynamic according to the TwinSAFE configuration in
the TwinCAT System Manager
EL6930 supply voltage
24 V
DC
(-15%/+20%)
Current consumption from the E-bus
approx. 188 mA
Power dissipation of the terminal
typically 1 W
Dimensions (W x H x D)
12 mm x 100 mm x 68 mm
Weight
approx. 50 g
Permissible ambient temperature (operation)
0
℃
to +55
℃
Permissible ambient temperature
(transport/storage)
-25
℃
to +70
℃
Permissible air humidity
5 % to 95 %, non-condensing
Permissible air pressure
(operation/storage/transport)
750 hPa to 1100 hPa
Climate category according to EN 60721-3-3
3K3
Permissible level of contamination
level of contamination 2
(comply with the chapter Cleaning)
Impermissible operating conditions
TwinSAFE terminals must not be used under the
following operating conditions:
•
under the influence of ionizing radiation
•
in corrosive environments
•
in an environment that leads to
unacceptable soiling of the Bus Terminal
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
according to EN 61000-6-2 / EN 61000-6-4
Shocks
15 g with pulse duration 11 ms in all three axes
Protection class
IP20
Permitted operating environment
control cabinet or terminal box with minimum
protection class IP54 according to IEC 60529
Permissible installation position
see section Installation position
Approvals
CE, TÜV SÜD