BECKHOFF BC3100 User Manual
Page 25

PROFIBUS-DP basics
BC3100
25
RS-485
Data transfer technology
to the Profibus standard
RS485 fundamental characteristics:
Network
topology
Linear bus, active bus terminator at both ends,
branch lines are possible
Medium
Shielded twisted cable, shielding may be
dispensed with in suitable environments
(electromagnetic compatibility)
Number of stations
32 stations in each segment without repeaters,
extendible to 127 with repeaters
Max. bus length
without repeaters
9.6, 19.2, 93.75 kBaud = 1200 m
187.5 kBaud = 1000 m
500 kBaud = 400 m
1500 kBaud = 200 m
3, 6 12 Mbaud = 100 m
with repeaters
Using repeaters (line amplifiers) increases the
max. bus length to the order of 10 km. The
number of possible repeaters is at least 3 and
may be up to 10, depending on the
manufacturer
Transfer rates
9.6, 19.2, 93.75, 187.5, 500, 1500 Kbit/s, up to
12 Mbit/s in discrete steps
Plug
9-Pin D-Sub plug
Pin assignments of the
D-Sub socket
1
6
5: GND
3: RxD/TxD- P
8: RxD/TxD- N
Cables for
PROFIBUS DP and
PROFIBUS FMS
In systems which contain more than two stations, all the subscribers are
connected in parallel. The bus cable must always be terminated at the
ends of the lines, to prevent reflections and the transmission problems they
cause.
In order to loop the cable through without any gaps it is necessary to affix
two cables within one plug. Siemens’ SINEC L2 bus connections are very
suitable for this. These SINEC plugs are constructed to accommodate two
bus cables with the corresponding wire terminals and shielding. At the end
of the line you can use a small switch in the plug to activate the terminating
resistor. Please observe the manufacturer’s assembly instructions.
You should also note that the terminating resistor requires a 5 V power
supply for optimal operation. This means that if the plug is removed from
the bus coupler, or the power supply of the bus coupler fails, the level at