Product description

12

C9900-G0xx

Three-button PCB

Fig. 7: Three-button PCB

The three-button PCB has two K-bus interfaces (1, CON400 & CON401), which are assigned ex factory.
The outer connection strips (2, CON600 & CON601) are used for power supply for the indicator lamps,
connection strip 4 is available for customer use. The bridges between the button PCBs are assigned ex
factory. The power supply has to be provided by the customer. One of the two N/O contacts of each
button is available for customer use via a connection strip (3, CON603). At a further connection strip (4,
CON602) three digital inputs are available for customer use, which are transferred via the K-bus. The 24
V supply has to be provided by the customer. The PCB also features a DIP switch (5, SW600), which is
explained in section 2.5.

The pin assignments for connection strips 2, 3 and 4 are listed in Table 2.

Connection
strip

Terminal
point

Description

1

1

24 V DC

2 0

V

3

1

Input N/O contact 1

2

Output N/O contact 1

3

Input N/O contact 2

4

Output N/O contact 2

5

Input N/O contact 3

6

Output N/O contact 3

1

24 V output

2

Digital input 1

3

24 V output

4

Digital input 2

5

24 V output

6

Digital input 3