beautypg.com

BECKHOFF CX1020 User Manual

Page 41

background image

Product

overview

Embedded PC

39

CX1020-N030/40 connections

The CX1020-N030 system interface features two RS232 interfaces, COM1 and COM2 (9 pin Sub-D plug connector).
If there is need for more than two serial interfaces two further RS232 interfaces, COM3 and COM4 (9 pin Sub-D plug
connector) can be added to the system via the system interface CX1020-N40. The maximum baud rate on all
channels is 115 kBit. The pin assignment for all interfaces is equal and described below. The interface parameter can
be set in the operating system or in the PLC program.

RS232 COM interface (connector):

Pin assignment COM interface:

PIN

Signal

Type

Description

1

DCD

Signal in

Data Carrier Detected

2

RxD

Signal in

Receive Data

3

TxD

Signal out

Transmit Data

4

DTR

Signal out

Data Terminal Ready

5 GND

Ground

Ground

6

DSR

Signal in

Dataset Ready

7

RTS

Signal out

Request to Send

8

CTS

Signal in

Clear to Send

9

RI

Signal in

Ring Indicator

Note


The system interface CX1020-N30 can only be used instead and not simultaneously with system
interface CX1020-N031.
The system interface CX1020-N40 can only be used instead and not simultaneously with system
interface CX1020-N041.

This manual is related to the following products: