beautypg.com

Instructions – Basler Electric APR63-5 User Manual

Page 3

background image

FIELD FLASHING

When the generator is operated with the regulator for
the first time, the polarity of the generator’s residual
magnetism may not be correct or the magnitude may
not be enough for reliable voltage buildup. If the
generator voltage does not build up, stop the prime
mover and proceed as follows:

1.

With the prime mover at rest, apply an
ungrounded dc source of not more than
48 Vdc to terminals F+ and F– in series with a
limiting resistor. Use 1

Ω of resistance for

each volt from the dc source. The resistor
should have a power rating of at least 1 watt
per volt.

2.

Allow approximately 30 seconds to elapse
before removing the dc source.

3.

Start the prime mover and measure the
voltage at regulator terminals 3 and 4. If the
voltage is greater than 6 Vac, voltage buildup
should occur. Repeat the flashing procedure if
less than 6 Vac is measured.

OPERATIONAL TEST

If desired, perform the following steps to perform a
bench test of APR 63-5 operation.

1.

Connect the APR 63-5 and apply 240 Vac as
shown in Figure 7.

2.

Rotate the VOLT control fully counter-
clockwise. The lamp should not be lit.

3.

Rotate the VOLT control fully clockwise. The
lamp should be lit.

4.

Rotate the VOLT control counterclockwise
until the lamp turns off.

Figure 1. Frequency Compensation Curves

Figure 2. Typical Inverse Time Characteristic Curve

0

0

10

20

30

40

50

60

20

40

60

80

100

120

Frequency (Hz)

(%

F

ro

m

N

o

m

in

a

l)

G

e

n

e

ra

to

r

O

u

tp

u

t

D2717-05

50 Hz

60 Hz

“Corner Frequency”

T

im

e

D

e

la

y

(

s

e

c

o

n

d

s

)

Field Voltage (dc)

1

2

3

4

5

6

8

10

20

30

40

50

60

80

100

70

200

300

400

500

80

90

100

110

120

130

140

150

135 ±5

D2717-06

Publication

9168700991

Revision

G

Instructions

Date

04/14

Page

3 of 6