Characteristic Data
Step 1. Adjust the current source phase angle for each of the values indicated in Table 5-3. Record the
magnitude of current required to receive each pickup indication. To measure pickup for each
phase angle setting, slowly increase the current magnitude from zero or a value less than the
pickup value until the PICKUP LED illuminates and an output contact operation occurs.
Table 5-3. Current Magnitudes Required for Pickup
Current Source Phase
Angle Setting (Degrees)
Equivalent System Power
Factor Angle (Ө) In Degrees
Current Magnitude
Required for Pickup (Amps)
+20
–20
+30
–30
+40
–40
+50
–50
+60
–60
+70
–70
+80
–80
+90
–90
+100
–100
+110
–110
+120
–120
Step 2. With the above recorded data, calculate P (watts) and Q (vars), as follows, for each recorded
pickup value.
( )
θ
cos
3
L
LL
I
V
P
=
( )
θ
sin
3
L
LL
I
V
Q
=
Where:
V
LL
= voltage measured in the test setup of Figure 5-2
I
L
= current measured in the test setup of Figure 5-2
Ө
= the (–) angle setting of the current source
NOTE
With the test setup as specified, the current source phase angle setting simulates
a leading power factor angle, i.e., Ө < 0.