Output contacts, Power supply, Output – Basler Electric BE1-40Q User Manual
Page 13: Contacts, Power, Supply -5

Figure 1-5. Typical Relay Response Time for Time Dial Settings
Output Contacts
Resistive Ratings
120 Vac:
Make, break, and carry 7 Aac continuously
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
Power Supply
Power supply types and specifications are listed in Table 1-2.
Table 1-2. Power Supply Ratings
Type
Nominal
Input Voltage
Input Voltage Range
Burden at Nominal
O (midrange)
48 Vdc
24 to 150 Vdc
1.9 W
P (midrange)
125 Vdc
24 to 150 Vdc
2.2 W
120 Vac
90 to 132 Vac
18.4 VA
R (low range)
24 Vdc
12 to 32 Vdc
∗
1.9 W
S (midrange)
48 Vdc
24 to 150 Vdc
1.9 W
125 Vdc
24 to 150 Vdc
2.2 W
T (high range)
250 Vdc
68 to 280 Vdc
2.3 W
240 Vac
90 to 270 Vac
32.1 VA
∗ Type R power supply initially requires 14 Vdc to begin operating. Once operating, the input voltage may
be reduced to 12 Vdc and operation will continue.
9171500990 Rev N
BE1-40Q General Information
1-5