beautypg.com

Led display, Password function, Synchronous communication protocol & auto id setup – Delta Electronics DTC2000 Series User Manual

Page 2: Rs-485 communication, Installation, How to set up current input

background image

Mode

Alarm Type

Alarm Output Operation

2

Alarm output will be enabled when the temperature reaches the upper limit.
y

Alarm will be enabled when the PV exceeds SV + AL-H.

ON

OFF

SV

AL-H

3

Alarm output will be enabled when the temperature reaches the lower limit.
y

Alarm will be enabled when the PV falls below SV – AL-L.

ON

OFF

AL-L

SV

4

y

Alarm will be enabled when the PV is between SV + AL-L and SV – AL-L.

ON

OFF

AL-L

SV

AL-H

5

Alarm output will be enabled when the temperature reaches the absolute
value of the upper and lower limits.
y

Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.

ON

OFF

AL-L

AL-H

6

Alarm output will be enabled when the temperature reaches the absolute
value of the upper limit.
y

Alarm will be enabled when the PV exceeds AL-H.

ON

OFF

AL-H

7

Alarm output will be enabled when the temperature reaches the absolute
value of the lower limit.
y

Alarm will be enabled when the PV falls below AL-L.

ON

OFF

AL-L

8

Standby upper/lower limit alarm
y

Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or

falls below SV – AL-L.

ON

OFF

AL-L

AL-H

SV

9

Upper limit standby alarm
y

Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.

ON

OFF

SV

AL-H

10

Lower limit standby alarm
y

Alarm will be enabled when the PV reaches SV and falls below SV – AL-L

ON

OFF

AL-L SV

11

Upper limit hysteresis alarm
y

Alarm will be enabled when the PV exceeds SV + AL-H and disabled when

the PV falls below SV + AL-L.

ON

OFF

AL-H

AL-L

12

Lower limit hysteresis alarm
y

Alarm will be enabled when the PV falls below SV – AL-H and disabled

when the PV exceeds SV – AL-L.

ON

OFF

AL-H

AL-L

Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L
(1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H).

 

LED Display

1. When power is normal, POWER LED will be on.
2. After DTC1000/2000 is switched on, all LED will be on. The communication protocol will be displayed in 1 second,

followed by the communication address in the next second.

3. RUN LED is on when the control is executing.
4. ERROR LED is on when errors occur in input, memory or communication.
5. When an output is executing, its corresponding output LED will be on.
6. AT LED flashes when PID parameters are being auto-tuned.
7. RX LED flashes when DTC1000/2000 receives communication signals. TX LED flashes when DTC1000/2000

sends out communication signals.

Communication protocol displayed on LED after the power of DTC1000/2000 is switched on:

AT

TX

RX

O1

O2

Err

Run

000: 2,400bps 001: 4,800bps 010: 9,600bps
011: 19,200bps 100: 38,400bps

Parity 00: None 01: Even
10: Odd

0: ASCII
1: RTU

0:2 Stop bits
1:1 Stop bit

Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code.

 

Password Function

The default setting of the password is disabled. To enable the password function, enter the 4-character password in the
specific communication address. The password is protected by 3 levels.
1. Level 1: Only LED status, SV and PV can be read. No settings can be modified.
2. Level 2: Only LED status, SV and PV can be read. Only SV can be modified.
3. Level 3: All SV can be read. Only SV and auto-tuning can be modified.
4. Level 4: No password protection.
When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the
corresponding password (in 106BH ~ 106DH). After DTC1000/2000 is switched off, the protection will return to Level 1.
To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H).
The password protection level can be read in 106EH ~ 1070H:

bit

b0

b1

b2

b3

b4

b5

b6

Status Level

1

Level 2

Level 3

Level 1 locked

Level 2 locked

Level 3 locked

Unlocked

bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status.

 

Synchronous Communication Protocol & Auto ID Setup

This function allows the user to set the communication protocol of DTC2000 to the same protocol as set in the first
DTC1000. The station IDs of DTC1000/2000 are arranged in decreasing order. Follow the steps below.
1. Set the auto communication ID of DTC1000 to “1” (communication address: 1022H).
2. Switch off DTC1000 before connecting it to DTC2000. Switch it on again.
3. Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01.
4. This function will consume 3 ~ 5 seconds more when you switch on your DTC.

 

RS-485 Communication

1. Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps;
2. Does not support 7, N, 1 / 8, E, 2 / 8, O, 2 communication format;
3. Communication protocol: Modbus ASCII/RTU;
4. Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of

data), 05H (write 1 bit into register).




Address

Setting

Content

Explanation

1000H

Present temperature value (PV)

Unit: 0.1 degree. Analog input: 1EU.
The read values below indicate the occurrence of errors:
8002H: Temperature not acquired yet
8003H: Temperature sensor not connected
8004H: Incorrect sensor type
8006H: Unable to acquire temperature, ADC input error
8007H: Unable to read/write the memory

1001H

0

Set point (SV)

Unit: 0.1 degree. Analog input: 1EU.

1002H

6,000

Upper-limit of temperature range

The content shall not be bigger than the range. Unit: 0.1°

1003H

-200

Lower-limit of temperature range

The content shall not be smaller than the range. Unit: 0.1°

1004H

12

Input sensor type

See the table in “Input” section.

1005H

0

Control method

0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID

1007H

4

Control cycle of Output 1

0 ~ 99, 0: 0.5sec

1008H

4

Control cycle of Output 2

0 ~ 99, 0: 0.5sec (Invalid when the 2 outputs are the same
control.)

1009H

476

Proportional band value

1 ~ 9,999, Unit: 0.1°. Analog input: 1EU

100AH

260

Ti value

0 ~ 9,999

100BH

41

Td value

0 ~ 9,999

100CH

0

Default integration value

0 ~ 1,000, Unit: 0.1%

100DH 0

Offset compensation value for proportional
control (when Ti=0))

0 ~ 1,000, Unit: 0.1%

100EH

100

COEF setting when in dual control output

1 ~ 9,999, Unit: 0.01

100FH 0

Deadband setting when in dual control
output

-999 ~ 9,999, Unit: 0.1° or 1EU

1010H

0

Hysteresis of Output 1

0 ~ 9,999, Unit: 0.1° or 1EU

1011H

0

Hysteresis of Output 2

0 ~ 9,999, Unit: 0.1° or 1EU

1012H

0

Read/write output percentage of Output 1

Unit: 0.1%. “Write” is only applicable in manual mode.

1013H

0

Read/write output percentage of Output 2

Unit: 0.1%. “Write” is only applicable in manual mode.

1014H

0

Upper-limit regulation for analog linear output 1 scale = 2.8μA = 1.3mV

1015H

0

Lower-limit regulation for analog linear output 1 scale = 2.8μA = 1.3mV

1016H

0

Temperature offset regulation value

-999 ~ +999, Unit: 0.1° or 1EU

1020H

0

Output mode for Alarm 1

See “Alarm Output” section.

1021H

0

Output mode for Alarm 2

See “Alarm Output” section.

1022H

0

Communication flag auto-set

0: Communication banned, 1: Communication auto-set

1024H

40

Upper limit for Alarm 1

See “Alarm Output” section.

1025H

40

Lower limit for Alarm 1

See “Alarm Output” section.

1026H

40

Upper limit for Alarm 2

See “Alarm Output” section.

1027H

40

Lower limit for Alarm 2

See “Alarm Output” section.

102AH

Read/write status

b1: ALM2, b2:

°C, b3:

°F, b4: ALM1, b5: O2, b6:O1, b7: AT

102CH

0

Positive/negative proportional output

0: positive, 1: negative

102EH

LED status

b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT

102FH

Software version

V1.00 is indicated as 0x100

1030H

0

No. of start pattern

0 ~ 7

1032H

Remaining time of the executed step

Unit: second

1033H

Remaining time of the executed step

Unit: minute

1034H

No. of currently executed step

0 ~ 7

1035H

No. of currently executed pattern

0 ~ 7

1037H

1,000

Upper limit of proportional output

0 ~ 100% upper limit of analog output, Unit: 0.1%

1038H

0

Lower limit of proportional output

0 ~ 100% lower limit of analog output, Unit: 0.1%

1040H~

1043H

7

Number of steps in a pattern

0 ~ 7 = N refers to the pattern will be executed from Step 0
to Step N.

1050H~

1053H

0

Additional number of cycles for a pattern

0 ~ 199 refers to the pattern will be executed for 1 ~ 200

times.

1060H~

1063H

0

No. of the link pattern for the current
pattern

0 ~ 8, 8 refers to end of the program. 0 ~ 7 refers to the
next pattern No. following the current pattern.

1068H

1

Run/Stop setting

0: Stop, 1: Run, 2: Program end, 3: Program hold

1069H

0

Control selection of Output 1

0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output

106AH

0

Control selection of Output 2

0: Heating, 1: Cooling, 2: Alarm

106BH 0

Unlock Level 1 password protection.
Read/write allowed

Shall be the same as Level 1 password (106E)

106CH 0

Unlock Level 2 password protection. Use
Level 3.

Shall be the same as Level 2 password (106F)

106DH 0

Unlock Level 3 password protection. Use
Level 2

Shall be the same as Level 3 password (1070)

106EH 0

Unlock Level 1 password protection/Set up
password

Unlock password before setting it up.

106FH 0

Unlock Level 2 password protection/Set up
password

Unlock password before setting it up.

1070H 0

Unlock Level 3 password protection/Set up
password

Unlock password before setting it up.

1071H

1

Read/write communication address

1 ~ 247

1072H

0

Read/write communication format

1: RTU, 0: ASCII

1073H 2

Read/write

communication speed

0 ~ 4: 2,400 ~ 38,400

1074H

1

Read/write communication data length

0: 8 bits, 1: 7 bits

1075H

1

Read/write parity bit

0: None, 1: Even, 2: Odd

1076H

1

Read/write stop bit

0: 2 stop bits, 1: 1 stop bit

2000H~

203FH

0

SV temperature for Pattern 0 ~ 7.

SV for Pattern 0 is set in 2000H ~ 2007H

Unit: 0.1°

2080H~

20BFH

0

Execution time for Pattern 0~7.
Time for Pattern 0 is set in 2080H ~ 2087H

0 ~ 900 (1 scale = 1 minute)

5. Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the

bit as 1. 0000H sets the bits data to “0”).

0811H

Temperature unit display

0:°F, 1: °C (Default)

0813H

Read/write auto-tuning status

0: End (Default), 1: Start

0814H

Run/Stop setting

0: Stop, 1: Run (Default)

0815H

Program hold flag

1: Program hold

0816H

Program stop flag

1: Program stop

6. Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word.

y

ASCII Mode

Read Command

Read Response Message

Write Command

Write Response Message

Start word

’:’ ’:’

Start word

’:’ ’:’

Start word

’:’

’:’

Start word

’:’ ’:’

Machine address 1

‘0’ ‘0’

Machine address 1

‘0’ ‘0’

Machine address 1

‘0’ ‘0’

Machine address 1

‘0’ ‘0’

Machine address 0

‘1’ ‘1’

Machine address 0

‘1’ ‘1’

Machine address 0

‘1’ ‘1’

Machine address 0

‘1’ ‘1’

Command 1

‘0’ ‘0’

Command 1

‘0’ ‘0’

Command 1

‘0’ ‘0’

Command 1

‘0’ ‘0’

Command 0

‘3’ ‘1’

Command 0

‘3’ ‘1’

Command 0

‘6’ ‘5’

Command 0

‘6’ ‘5’

‘1’ ‘0’

‘0’ ‘0’

‘1’ ‘0’

‘1’ ‘0’

‘0’ ‘8’

Length of response data

(byte)

‘4’ ‘2’

‘0’ ‘8’

‘0’ ‘8’

‘0’ ‘1’

‘0’ ‘1’

‘0’ ‘1’

‘0’ ‘1’

Read staring address of

data/bit

‘0’ ‘0’

‘1’ ‘7’

Write data address

‘1’ ‘0’

Write data address

‘1’ ‘0’

‘0’ ‘0’

‘F’ ‘0’

‘0’ ‘F’

‘0’ ‘F’

‘0’ ‘0’

Data content in

1000H/081xH

‘4’ ‘1’

‘3’ ‘F’

‘3’ ‘F’

‘0’ ‘0’

‘0’

‘E’ ‘0’

‘E’ ‘0’

Read length of data/bit

(word/bit)

‘2’ ‘9’

‘0’

To write data content

‘8’ ‘0’

Write data content

‘8’ ‘0’

LRC1 check

‘E’ ‘D’

‘0’

LRC1

‘F’ ‘E’

LRC1

‘F’ ‘E’

LRC0 check

‘A’ ‘D’

Data content in 1001H

‘0’

LRC0

‘D’ ‘3’

LRC0

‘D’ ‘3’

End word 1

CR CR

LRC1 check

‘0’ ‘E’

End word 1

CR CR

End word 1

CR CR

End word 0

LF LF

LRC0 check

‘3’ ‘4’

End word 0

LF LF

End word 0

LF LF

End word 1

CR CR

End word 0

LF LF

y

LRC Check

LRC check sums up from “machine address” to “data content”, e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2’s
complement EA.

y

RTU Mode

Read Command

Read Response Message

Write Command

Write Response Message

Machine address

01H 01H

Machine address

01H 01H

Machine address

01H 01H

Machine address

01H 01H

Command 03H 01H

Command 03H 01H

Command 06H 05H

Command 06H 05H

10H 08H

10H 08H

10H 08H

Read start address

of data

00H 10H

Length of response

data (byte)

04H 02H

Write data address

01H 10H

Write data address

01H 10H

00H 00H

01H 17H

03H FFH

03H FFH

Read length of data

(bit/word)

02H 09H

Data content 1

F4H 01H

Write data content

20H 00H

Write data content

20H 00H

CRC low byte

C0H BBH

03H

CRC low byte

DDH 8FH

CRC low byte

DDH 8FH

CRC high byte

CBH A9H

Data content 2

20H

CRC high byte

E2H 9FH

CRC high byte

E2H 9FH

CRC low byte

BBH 77H

CRC high byte

15H 88H

y

CRC Program Example

unsigned int reg_crc = 0xffff; i = 0;
while (length--)
{
reg_crc ^= RTUData[i];
i ++;
for (j = 0; j < 8; j++)
{

if (reg_crc & 0x01)

reg_crc = (reg_crc >> 1) ^ 0xA001;

else

reg_crc = reg_crc >> 1;

}
}
return(reg_crc);

 

Installation

How to connect maximum 8 DTC1000/2000 controllers by using DIN rail.

 

How to Set Up Current Input

For general input

For current input (4 ~ 20mA, 0 ~ 20mA)

JU MPER

PIN HEADER

JP1

DEFAU LT SETTING

J UMPER

PIN HEADER

JP1

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or

download the most updated version at http://www.delta.com.tw/industrialautomation

This manual is related to the following products: