I

NSTALLATION

(C

ONT

.)

Pellet Vent Termination (See the illustration below)

¥

Must have an approved cap (to prevent water from entering) or a 45

o

downturn

¥

If the termination is located on a windy side of the house, an approved house
shield is recommended to prevent soot from building up on the side of the house

¥

Must not be located where it will become plugged by snow or other material

A

Minimum 4' clearance below or beside any door or window that opens

B

Minimum 1' clearance above any door or window that opens

C

Minimum 2' clearance from any adjacent building

D

Minimum 7' clearance above any grade when adjacent to public walkways

E

Minimum 2' clearance above any grass, plants, or other combustible materials

F

Minimum 3' clearance from any forced air intake of any other appliance

G

Minimum 2' clearance below eaves or overhangs

H

Minimum 1' clearance horizontally from combustible wall

X

Must be a minimum of 2' above the roof

C

B

D

E

A

G

X

A

F

H

O

UTSIDE

A

IR

R

EQUIREMENTS

¥

Required for mobile homes

¥

Must not be drawn from an enclosed space (garage, unventilated crawl space)

¥

Must not be over 15' long

¥

Must be made with 1 3/4" diameter or larger
metal or aluminum duct with a metal screen
attached to the end to keep out rodents
(P.V.C. or other combustible materials may
not be used)

¥

The outside air connects to the outside air
inlet 3 3/16" from the center of the stove and
the distance listed below for the type of legs
used (see the illustration to the right):

Pedestal

13 1/4"

Brass Legs

9 7/8"

Cast Legs

9 7/8"

Black Legs

8 1/2"

Center Line

3 3/16"

See the Table

Outside Air Inlet
(1 3/4" Outside Dia.)