Installation – Avalon Firestyles 1080 CF Installation User Manual
Page 37

Installation
(for qualified installers only)
37
© Travis Industries
4090807
100-01193_003
Non-Combustible Facing
•
Non-combustible facing on the front of the fireplace must extend a minimum 17-1/4” from the
top of the glass frame. Above 17-1/4” combustibles may be used, but may not protrude more
than 3/4” from the non-combustible facing. Any combustible that protrudes more than 3/4” is
considered a mantel and must meet mantel clearances.
•
Non-combustible facing on the front of the fireplace must extend a minimum 6-1/2” to each
side of the glass frame. Beyond 6-1/2” combustibles may be used, but may not protrude more
than 3/4” from the non-combustible facing. Any combustible that protrudes more than 3/4” is
considered a side wall and must maintain the 11” side wall clearances.
•
The maximum depth for non-combustible facing is 6” (includes the cement board).
Combustible Material
(drywall, etc.)
Fiber Board
Fireplace
Glass Frame
17-1/4” Min.
50” Min.
(from base of fireplace)
Non-Combustible Facing
(tile, rock, marble, etc.)
Figure 26