10.2 Single channel switching
Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.
Configured to presence detection: Turns on automatically with occupancy. Press and release down
switch to turn off. Press and release up switch to turn back on. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Press and release down
switch to turn off. Turns off after occupancy.
Channel mode: Set to ―Switch only‖
Switch mode: Set to ―2 position switch together‖. Note: a single position switch can be used instead to
toggle the output, set to ―1 position switch separate‖.
L/OUT
L
N
SW1/UP
+
-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(1-10V)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
L/OUT
L
N
SW1/UP
SW2
DOWN
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
LUMINAIRE
(NON-DIMMING)
+
-