5
-
Current Transformer Input:
5 A ,
(Transformer I
n
/5A)
NOTE: Minimum cable section 2.5mm
2
.
-
Compliance with Standards
UNE EN 61921 and EN-61642
-
Protection elements:
Power Fuses
Type gL, NH gauge (minimum 1,5
×
I
nominal
)
Reactor thermostat:
90ºC ±5ºC
Insulation
3 kV /50 Hz
Breaking capacity
10A / 250 V CA, resistive load
-
Capacitor characteristics:
Capacity tolerance:
± 5%
Insulation level to earth:
3 kV /50 Hz
Impulse test:
15 kV , 1,2/50 µs standard wave
Protection elements:
Internal fuses and over-pressure system
Compliance with Standards
UNE EN 60831
-
Reactor characteristics:
Inductor tolerance:
± 5%
Nominal working voltage
standard 500 V (RMS value)
Saturation current
standard at 1.4 I
n
,
∆
L=5%
(Others in RBX)
Level of insulation between:
3kV /50Hz; 15kV ; 1,2/50 µs standard wave
phases and to earth
Max. overload
Σ
(n.I
n
)
2
20% permanent; Transient (1 min.) 2 I
n
4.3
Environmental Characteristics
-
Capacitor max. temperature
Category C in accordance with EN 60831-1
Maximum for 1h
50ºC
24h average
40ºC
Annual average
30ºC
-
Max. temperature of reactors
In accordance with IEC 60076-6
Maximum environmental temperature
60ºC
Indoor temperature at I
n
<110ºC
Protection thermostat
90 ºC
-
Cabinet ventilation
For outdoor t
amb
> 30ºC, forced ventilation
must be used for the cabinet
-
Maximum relative humidity:
80%
-
Altitude:
1000 m
(For higher altitudes, always
maintain forced ventilation)
4.4
Mechanical features
-
Protection degree:
Marked on the label:
-
Paint
Oven dried epoxy type
-
Standard colours
RAL 7035 Grey ; RAL 3005 Maroon
4.5
External dimensions and weights.
Dimensions (mm)
Model
Width
Height
(*)
Depth
Max weight
(kg)
FRS
700
1000
380
215
FR4
800
1900
650
460
FR6
1100
1900
650
685
FR8
1500
1900
650
1000
Fig. 4-2.- Dimensions
FR12
2200
1900
650
1389
(*)
Maximum dimensions