beautypg.com

CIRCUTOR T3V Series User Manual

Page 4

background image

--------- EARTH RESISTANCE TESTER

T-3V

------- Page No. 3

-

1.2.- Specifications

Measuring system

Ground earth resistance using constant
current inverter.
800 Hz, 2 mA approx.

Earth voltage

0-200 V AC., 40 – 500 Hz.

Floor resisitivity

Range and resolution:
0 ~ 20

Ω (0.01 Ω)

0 ~ 200

Ω (0.1 Ω)

0 ~ 2000

Ω (1 Ω)

Earth voltage accuracy

± (1% read. + 2 dig.)

Floor resistivity accuracy

± 0.1 Ω or (if higher);
± (2% read. + 2 dig.)

Safety standards

IEC – 1010 (EN61010).

Battery low indicator

The symbol “B” appears on the display.

Reading memory indicator

The symbol “DH” appears on the display.

Over-range indicator

“1” in the most significant digit (MSD).

Open circuit indicator

The operating indicator (2) remains off.

Timer (self-disconnection)

After about 3 ~ 6 minutes without operating
any check.

Indicator

3 ½ digit LCD (2000 accounts)

Power supply

6 x 1.5 V batteries (R6C).

Sizes

A. 163 x Al. 100 x Pr. 50 mm

Weight:

Approx. 800 g (including batteries)

Accessories

Test Pins (red – 15 m, yellow – 10 m, green –
5 m) auxiliary earth rods, carrying case,
instruction manual.