Modbus variables, Write commands – CIRCUTOR ReadWatt Series User Manual
Page 15
![background image](https://www.manualsdir.com/files/767718/content/doc015.png)
4�3�3�- WRITE COMMANDS
ReadWatt supports the integer type write functions: 0x10.
The unit's
MODBUS variables are specified in
.
Example: Changing the MODBUS address of peripheral 01 to the address
0x000A
.
We will send the following
MODBUS frame:
Address
Func-
tion
Initial log
Log no�
No� bytes
Data
CRC
01
10
0008
0001
02
000A
CRC
The unit will respond to us with the next frame:
Address
Func-
tion
Initial log
Log no�
CRC
01
10
0008
0001
CRC
Note: The values are shown in hexadecimal.
The number of logs to write must be the same as the size of the variable that is being
accessed.
It is possible to write several consecutive addresses, if the request meets the correct format.
4�3�4�- MODBUS VARIABLES
Table 4: Readwatt MODBUS variables�
Description
Address
(Hexadecimal)
Size
Read/Write
Default value
Modbus Address
0x0008
16 bits
Read/Write
10
Transmission speed
(Baudrate)
0x010C
16 bits
Read/Write
0: 9600
1:19200
2: 38400
0: 9600
Serial no.
0x0060
32-bit
Read
-
Maximum width of impulses in ms
0x0106
16 bits
Read/Write
250 ms
Minimum width of impulses in ms
0x0107
16 bits
Read/Write
2 ms
No. of input impulses per output
impulse
0x0108
16 bits
Read/Write
10
Ratio between input impulses and
kWh (kvarh)
0x0109
16 bits
Read/Write
1000
Transformation ratio
(1)
0x010A
16 bits
Read/Write
1
Output impulse width in ms
0x010B
16 bits
Read/Write
100 ms
Instantaneous values
Impulse log
0x0600
64 bits
Read
-
kWh (kvarh) log
0x0604
64 bits
Read
-
15
Instruction Manual
ReadWatt