3.3.4 Programmable Outputs

The TSM17P drives feature three optically isolated digital outputs (Y1 to Y3). Y1, Y2 and Y3 share

a common terminal YCOM.
• Y1 can be set to signal a fault condition.
• Y2 can be set to indicate whether the motor is in position(dynamic).
• Y3 can be set to control a motor brake, or to provide an output frequency proportional to motor

speed (tach signal) or to provide a timing output (50 pulses/rev) or to indicate whether the

motor is in position(static)

These outputs can also be turned on and off by program instructions like Set Output (SO). The

output can be used to drive LEDs, relays and the inputs of other electronic devices like PLCs and

counters. Diagrams of various connection types follow.

Do not connect the outputs to more than 30 volts. The current through each output terminal must

not exceed 100mA.

+

-

Y1

YCOM

5 - 24

volt DC

Power

Supply

Connecting a Sinking Output

Load

TSM17

COM

IN

Y2

YCOM

PLC

Connecting a Sourcing Output

5 - 24VDC

Power Supply

TSM17

+

-

+

-

5 - 24

volt DC

Power

Supply

Driving a Relay

Y3

YCOM

relay

1N4935 suppresion diode

TSM17