5 installing the unit, 6 pmi 509 installation, Installing the unit – Pilz PMI 509 User Manual
Page 22: Pmi 509 installation

Installation
Operating Manual PMI 5
1002241EN05
22
5.5
Installing the unit
When installing the unit, please note the following:
}
For stability reasons, the front panel, console or control cabinet should have a wall
thickness of at least 2.5 mm.
}
To avoid a buildup of heat, a distance of a 10 cm/3.94" should be kept free all round
the system.
}
Ensure the information given for the ambient and operating temperatures in the tech
nical details is observed.
}
IP65 protection can only be guaranteed when
–
the fixing screws are sufficiently tightened (min. 0.2 Nm).
–
the gasket is not damaged.
–
the wall thickness is at least 2.5 mm.
}
Protect the system against falling down, i.e. ensure that the fixing screws are firmly
tightened.
5.6
PMI 509 Installation
Fig.: PMI 509 Installation
NOTICE
The torque setting for the fixing screws may not exceed 0.3 Nm.