2 call web server, 3 exchange gateway, Call web server – Pilz PSSnet GW1 MOD-EtherCAT User Manual
Page 34: Exchange gateway
Operation
Operating Manual PSSnet GW1 MOD-EtherCAT
1002692-EN-02
34
}
Access without a password is not possible.
}
User names and passwords can be changed.
}
If the password is changed and the new password is forgotten, you have no longer the
option to access the web server via the gateway. In this case, the gateway has to be
sent to Pilz and reset to the original delivery status. Thereby all settings will be lost.
Ensure that the (new) password is saved reliably once the password has been
changed.
}
Ensure that the configuration with the passwords of the delivery status is saved
before
changing the passwords.
1. Call up the web server.
2. Copy these files to a PC using FTP:
– eth_cfg.xml (Ethernet configuration),
– password.xml (user definition).
Call web server
1. Connect the Gateway to the PC.
2. Call up the following HTML page:
–
http://192.168.0.xxx
– For xxx, enter the value that you have set as the last byte of the IP address.
3. Enter the user name and password correctly and log on to the web server.
4. Select the option you require from the options in the overview and then follow the in-
structions.
Exchange Gateway
When exchanging the Gateway, the current configuration should be saved first, so that the
configuration can be imported into the new Gateway.
Recommended procedure:
1. Call up the web server and save the configuration.
– Copy these files to a PC using FTP:
eth_cfg.xml (Ethernet configuration),
password.xml (user definition).
2. Switch off the supply voltage.
3. Disconnect all cables from the Gateway.
4. Remove the Gateway from the mounting rail.
5. Install the new Gateway in accordance with the Installation Manual,
6. Incorporate the Gateway into the network,
.
– Make sure that the settings for the IP address are exactly the same as they were on
the old module.
7. Copy the configuration data to the new Gateway via FTP.
8. Restart the Gateway via the web server.