beautypg.com

Pilz PSSnet GW1 MOD-EtherCAT User Manual

Page 22

background image

Function description

Operating Manual PSSnet GW1 MOD-EtherCAT
1002692-EN-02

22

EtherCAT

Byte

Modbus Register

Access type Meaning in EtherCAT

200a:043

4x01022

Low Byte RO

EtherCAT Link State Port 0

}

Upper nibble: Loop state

– 1 = Loop closed
– 2 = Loop open

}

Lower nibble: Link state

– 0 = No Link
– 1 = Link

e.g.: 0x10 = No link, Loop closed,

0x21 = Link, Loop open

200a:044

High Byte RO

Reserved

200a:045

4x01023

Low Byte RO

EtherCAT Link State Port 1

}

Upper nibble: Loop state

– 1 = Loop closed
– 2 = Loop open

}

Lower nibble: Link state

– 0 = No Link
– 1 = Link

e.g.: 0x10 = No link, Loop closed,

0x21 = Link, Loop open

200a:046

High Byte RO

Reserved

200a:047

4x01024

Low Byte RO

EtherCAT RUN State (LED ECAT-

Stat)

}

0 = LED off

}

1 = Init

}

2 = Pre-Operational

}

4 = Safe-Operational

}

8 = Operational)

Key to LED statuses

Display ele-

ments for device diagnostics [

33]

200a:048

High Byte RO

Reserved

200a:049

4x01025

Low Byte RO

EtherCAT ERR State (LED ECAT-

Stat)

}

0 = LED off (No Error)

}

1 = LED on (Error)

Key to LED statuses

Display ele-

ments for device diagnostics [

33]

200a:050

High Byte RO

Reserved

RO = Read Only