Function description
Operating Manual PSSnet GW1 MOD-EtherCAT
1002692-EN-02
22
EtherCAT
Byte
Modbus Register
Access type Meaning in EtherCAT
200a:043
4x01022
Low Byte RO
EtherCAT Link State Port 0
}
Upper nibble: Loop state
– 1 = Loop closed
– 2 = Loop open
}
Lower nibble: Link state
– 0 = No Link
– 1 = Link
e.g.: 0x10 = No link, Loop closed,
0x21 = Link, Loop open
200a:044
High Byte RO
Reserved
200a:045
4x01023
Low Byte RO
EtherCAT Link State Port 1
}
Upper nibble: Loop state
– 1 = Loop closed
– 2 = Loop open
}
Lower nibble: Link state
– 0 = No Link
– 1 = Link
e.g.: 0x10 = No link, Loop closed,
0x21 = Link, Loop open
200a:046
High Byte RO
Reserved
200a:047
4x01024
Low Byte RO
EtherCAT RUN State (LED ECAT-
Stat)
}
0 = LED off
}
1 = Init
}
2 = Pre-Operational
}
4 = Safe-Operational
}
8 = Operational)
ments for device diagnostics [
200a:048
High Byte RO
Reserved
200a:049
4x01025
Low Byte RO
EtherCAT ERR State (LED ECAT-
Stat)
}
0 = LED off (No Error)
}
1 = LED on (Error)
ments for device diagnostics [
200a:050
High Byte RO
Reserved
RO = Read Only