Mounting distances

When installing the device in the control cabinet / mounting space it is essential to maintain
a certain distance from the top and bottom, as well as to other heat-producing devices (see
diagram). The values stated for the mounting distances are minimum specifications.

20 mm

(0.787“)

20 mm

(0.787“)

Control cabinet wall / heat-producing devic

e

30 mm

(1.81“)

30 mm

(1.81“)

Control cabinet wall / heat-producing devic

e

Mounting distances

Supply voltage

The Gateway requires a 24 VDC supply.
To achieve the lowest possible residual ripple (≤ 5%), we recommend that you install a
three-phase bridge rectifier or regulated supply.
Protect the external power supply by fitting a fuse between the external power supply and
the control system. The size of the fuse will depend on the specification of the external
power supply, the conductor cross section and on local and national regulations.