beautypg.com

2 terminals, 3 terminal configuration, 4 interfaces – Pilz PSSnet GW1 MOD-EtherCAT User Manual

Page 29: 1 rj45 interface, Terminals, Terminal configuration, Interfaces, Rj45 interface

background image

Commissioning

Operating Manual PSSnet GW1 MOD-EtherCAT
1002692-EN-02

29

Spring-loaded terminals:

}

Minimum conductor cross section on field connection terminals = 0.2 mm

2

(AWG24),

}

Maximum conductor cross section on field connection terminals = 2.5 mm

2

(AWG12),

}

Terminal points per connection: 2,

}

Stripping length: 9 mm.

Terminals

The plug-in terminals for the inputs and outputs are not supplied with the system. You can
select between spring-loaded terminals and a screw connection.

Terminal configuration

Module supply

Terminal configuration

X4

4-pin female connec-

tor

1

+24 V infeed for module supply

1 2 3 4

2

0 V infeed for module supply

3

Not connected

4

Functional earth

Terminal configuration

Interfaces

The following minimum requirements must be met:

}

Ethernet standards (min. Category 5) 100BaseTX

}

Double-shielded twisted pair cable for industrial Ethernet use

}

Shielded RJ45 connectors (industrial connectors)

RJ45 interface

RJ45 socket, 8-pin

PIN

Standard

Crossover

8 1

1

TD+ (Transmit+)

RD+ (Receive+)

2

TD- (Transmit-)

RD- (Receive-)

3

RD+ (Receive+)

TD+ (Transmit+)

4

n.c.

n.c.

5

n.c.

n.c.

6

RD- (Receive-)

TD- (Transmit-)

7

n.c.

n.c.

8

n.c.

n.c.

Interface assignment of RJ45 socket

n.c. = not connected

6.2.2

6.3

6.4

6.4.1