29
Spring-loaded terminals:
}
Minimum conductor cross section on field connection terminals = 0.2 mm
2
(AWG24),
}
Maximum conductor cross section on field connection terminals = 2.5 mm
2
(AWG12),
}
Terminal points per connection: 2,
}
Stripping length: 9 mm.
Terminals
The plug-in terminals for the inputs and outputs are not supplied with the system. You can
select between spring-loaded terminals and a screw connection.
Terminal configuration
Module supply
Terminal configuration
X4
4-pin female connec-
tor
1
+24 V infeed for module supply
1 2 3 4
2
0 V infeed for module supply
3
Not connected
4
Functional earth
Terminal configuration
Interfaces
The following minimum requirements must be met:
}
Ethernet standards (min. Category 5) 100BaseTX
}
Double-shielded twisted pair cable for industrial Ethernet use
}
Shielded RJ45 connectors (industrial connectors)
RJ45 interface
RJ45 socket, 8-pin
PIN
Standard
Crossover
8 1
1
TD+ (Transmit+)
RD+ (Receive+)
2
TD- (Transmit-)
RD- (Receive-)
3
RD+ (Receive+)
TD+ (Transmit+)
4
n.c.
n.c.
5
n.c.
n.c.
6
RD- (Receive-)
TD- (Transmit-)
7
n.c.
n.c.
8
n.c.
n.c.
Interface assignment of RJ45 socket
n.c. = not connected