beautypg.com

Operating parameters, Heating mode, Cooling mode – WaterFurnace Envision2 NXW Chiller User Manual

Page 29

background image

29

ENVISION

2

NXW REVERSIBLE CHILLER INSTALLATION MANUAL

Operating Parameters

NOTE: Operating data based on normal conditions with 4 gpm/ton for the load and source.

NOTE: Operating data based on normal conditions with 4 gpm/ton for the load and source.

Heating Mode

Entering

Load Temp (

o

F)

Entering

Source Temp (

o

F)

Suction

Pressure (psig)

Discharge

Pressure (psig)

Superheat

(

o

F)

Subcooling

(

o

F)

60

30

75-100

200-215

10-12

10-13

50

100-125

200-215

12-14

8-12

70

125-150

215-230

14-18

8-12

90

150-165

230-255

25-30

8-12

80

30

75-100

285-300

10-12

10-13

50

100-125

300-315

12-14

8-12

70

125-150

315-330

14-18

8-12

90

150-165

330-345

25-30

8-12

100

30

85-110

365-380

10-12

7-11

50

110-135

385-400

12-14

7-11

70

135-165

400-415

14-18

3-7

120

50

110-135

485-500

12-14

7-11

70

135-165

500-515

14-18

3-7

1/30/14

Cooling Mode

Entering

Load Temp (

o

F)

Entering

Source Temp (

o

F)

Suction

Pressure (psig)

Discharge

Pressure (psig)

Superheat

(

o

F)

Subcooling

(

o

F)

50

30

80-90

140-175

15-20

3-6

50

90-100

200-235

11-15

6-9

70

100-110

250-285

11-15

9-12

90

100-120

330-365

8-12

12-14

110

110-130

430-465

8-12

14-19

70

30

80-90

150-185

15-20

3-6

50

90-100

210-245

11-15

6-9

70

100-110

260-295

11-15

9-12

90

110-120

340-375

8-12

12-14

110

110-140

440-485

8-12

14-19

90

30

80-90

150-185

15-20

3-6

50

90-100

210-245

11-15

6-9

70

100-110

260-295

11-15

9-12

90

110-120

340-375

8-12

12-14

110

30

90-100

160-195

40-45

3-6

50

110-130

220-255

30-40

6-9

1/30/14