Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
1
Total
Unit
FLA
Min
Circ
Amp
Min
Fuse/
HACR
Max
Fuse/
HACR
2
MCC
RLA
LRA
120
208-230/60/3
187/253
36.0
23.1
160.0
46.2
52.0
60.0
70
460/60/3
414/506
19.0
12.2
87.0
24.4
27.5
30.0
35
575/60/3
517/633
13.5
8.7
62.0
17.4
19.6
20.0
25
380/60/3
342/418
19.0
12.2
95.0
24.4
27.5
30.0
35
180
208-230/60/3
187/253
45.0
28.8
235.0
57.6
64.8
70.0
90
460/60/3
414/506
19.0
12.2
110.0
24.4
27.5
30.0
35
575/60/3
517/633
16.5
10.9
95.0
21.8
24.5
25.0
35
240
208-230/60/3
187/253
52.2
35.2
250.0
70.4
79.2
80.0
110
460/60/3
414/506
27.0
19.2
140.0
38.4
43.2
45.0
60
575/60/3
517/633
19.1
14.5
100.0
29.0
32.6
35.0
45
360
208-230/60/3
187/253
75.0
48.1
351.0
96.2
108.2
110.0
150
460/60/3
414/506
38.6
24.7
197.0
49.4
55.6
60.0
80
575/60/3
517/633
35.0
22.4
135.0
44.8
50.4
60.0
70
380/60/3
342/418
51.0
32.7
239.0
65.4
73.6
80.0
100
600
460/60/3
414/506
62.0
39.7
260.0
79.4
89.3
100.0
125
575/60/3
517/633
45.0
28.8
210.0
57.6
64.8
70.0
90
380/60/3
342/418
72.0
46.2
310.0
92.4
104.0
110.0
150
HACR circuit breaker in USA only
1
- MCC, RLA, & LRA rating per compressor. Breaker & FLA sized for both compressors.
2
- Equipment supplied with Class J fuses per minimum fuse size.
3/5/14
Compressor Protection Module
An electronic protection module is provided with
compressors utilized in model size 600. This module will
protect against phase reversal and phase loss at start-up.
Protection is active for 5 seconds after the first second
of compressor operation. In the event that either phase
sequencing or phase loss has occurred the following
blink sequence will display on the module.