NXW REVERSIBLE CHILLER INSTALLATION MANUAL

Power Fail Restart

When the controller is first powered up, the outputs will be

disabled for a random start delay. The delay is provided to

prevent simultaneous starting of multiple heat pumps. Once

the timer expires, the controller will operate normally.

Random Start Delay

This delay will be used after every power failure, as well as

the first time the compressor is started after the control exits

the unoccupied mode or the emergency shutdown mode.

The delay should not be less than 1 second and not longer

than 120 seconds. If the control is in test mode the random

start delay will be shortened to 5 seconds.

Lead Compressor Start Delay Time

The Lead Compressor Fixed On Delay Time will ensure that

the lead compressor output is not enabled for 90 seconds

after the control receives a call to start the compressor. This

delay is adjustable from 30 – 300 seconds over a BAS or a

MUI. If the control is in test mode the Lead Compressor Start

Delay Timer will be shortened to 5 seconds.

Lag Compressor Start Delay Time

The Lag Compressor Fixed On Delay Time will ensure that

the lag compressor output is not enabled for 90 seconds

after the control receives a call to start the compressor. This

delay is adjustable from 30 – 300 seconds over a BAS or a

MUI. If the control is in test mode the Lag Compressor Start

Delay Timer will be shortened to 5 seconds.

Compressor Minimum On Delay

The compressor minimum on delay will ensure that the

compressor output is enabled for a minimum of five (5)

minutes each time the compressor output is enabled. This will

apply in every instance except in the event the high pressure

switch is tripped, freeze protection, or emergency shutdown

then the compressor output will be disable immediately.

Compressor Minimum Off Delay Time

The compressor minimum off time delay will ensure that

the compressor output will not be enabled for a minimum

of five (5) minutes after it is disabled. This allows for

the system refrigerant pressures to equalize after the

compressor is disabled.

Sequence of Operation

Compressor Lead/Lag

Compressor lead/lag is a standard part of the FX10 control

system. The unit is shipped from the factory with lead/

lag enabled. Lead/lag can be activated through the unit

mounted user interface.

Heating Cycle

The control will run the unit in heating mode when there is a

command on the O/B terminal on the terminal board.

Cooling Cycle

The control will run the unit in cooling mode when there is no

command on the O/B terminal on the terminal board.

MUI Alarm History Reporting

If a fault occurs the fault will be recorded in history for

display on the medium user interface in the History Menu.

Each fault type will be displayed in the history menu with

a number between 0 and 3. A reading of 3+ will mean that

fault has occurred more than three times in the past. The

history menu can be cleared with a power cycle only. Alarm

date and time are not included in the history.