Mui menu navigation, Unit display and interface cont – WaterFurnace Envision2 NXW Chiller User Manual
Page 26
26
ENVISION
2
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Unit Display and Interface Cont.
MUI Menu Navigation
Welcome
Info Temp
Stat
Outputs
Settings
Maint
Alarm
ALM_History
Dual Stage Setpt
Reversible Chiller
PRODCWWE-10
MM/DD/YY
Info
Outputs
Comp 1 Status
ON
Comp 2 Status
OFF
RV Status
Heat
Acc 1 Status
OFF
Stg 1 Status
Normal
Stg 2 Status
Normal
EXPB01
OFF
EXPB02
OFF
EXPB07
OFF
Cp1 0
CP2 0
Outputs
Status
Unit Status
Auto
Y1 Status
OFF
Y2 Status
OFF
O Status
OFF
Emerg Shutdown OFF
Current Sens 1
OFF
Current Sens 2
OFF
Load Flow
OFF
Src Flow
OFF
Low Pres 1
ON
Hi Pres 1
NML
Low Pres 2
ON
Hi Pres 2
NML
Comp1 Low Limit NML
Comp2 Low Limit NML
Stat
Temperatures
Enter Load
77.2 ºF
Leave Load
51.0 ºF
Enter Source
70.0°F
Leave Source
66.0°F
Source Frz 1
77.8°F
Source Frz 2
30.0°F
Load Frz 1
30.0°F
Load Frz 2
30.0°F
Src Frz Setpt
30.0°F
LD Frz Setpt
30.0°F
Temp
Settings
Unit of Measure
F
CoolSetpt
XX.X
HeatSetpt
XXX.X
D NegThrshld
X.X
Int Rate
XXXXS
Mode
Aquastat
Stage Delay
XXX S
Sensor Select LWT
Gain
X.X
D PosThrshld
X.X
PIDY1 Ref
XXX
PID Y1 Diff
XX.X
PID Y2RefShift XX.X
PID Y2 Diff
XX.X
Settings
FP1
Log Off
FP2
Log Off
Int 1
XX.X
Temp Err
XX.X
RndmStrtDly
Run
Derivative
XX.X
Integ’r
Ena
PID Y1
Off
PID Y2
Off
D_Neg
Off
D_Pos
Off
O 2 Off O 4
Enum_0
Pos Err
Off
PID Out
XXX.X
Maintenance
Y1 Input
Off
Y2 Input
Off
B Input
Off
Emerg SD
Normal
Acc 1 Sel
On Comp
Lead/Lag Select On
Low Frz Setpt XX.X°F
Hi Frz Setpt
XX.X°F
Acc I Dly
XXXX S
LagCompDly
XXX S
Alarm
#Events
PreFrz1
0
Lo Press 1
0
Src Freeze 1
0
Ld Freeze 1
0
Bad Ld Sensor
0
Lo Press 2
0
Src Freeze 2
0
PreFrz 2
0
Hi Press 1
0
Bad Src Sensor
0
Ld Freeze 2
0
Hi Press 2
0
StrtFail 1
0
StrtFail 2
0
Alarm History
Maintenance
ALARM SUMMARY
^/High Pressure
Alarm
When in the stat page, press the
right arrow once to go this screen
NOTE: This FX10 application implements an alarm history which is reset
only by cycling power. This history shows on the Alm-History page. Any
alarm showing 2+ events has occurred more than 2 times.
Alarm lock-outs are reset by cycling power,
by pressing the “ESC” and
Return
keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes,
and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.