Maintenance Schedule
SECTION XV - Maintenance Schedule
Service Technician
At least on an annual basis the following main-
tenance should be performed by a qualified ser-
vice technician:
General
•
Attend to any reported problems.
•
Inspect the interior of the combustion
chamber; clean and vacuum if necessary.
•
Clean the condensate trap in the vent
system and fill with fresh water.
•
Check for leaks; water, gas, flue and
condensate.
•
Verify flue vent piping and air inlet pip-
ing are in good condition and sealed
tight.
•
Check primary system water pressure/
primary system piping/primary expan-
sion tank.
•
Check domestic water pressure/domes-
tic system piping/domestic thermal
expansion tank.
•
Check domestic and primary thermo-
stat settings.
•
Check ignition electrode (sand off any
white oxide; clean and reposition).
•
Check ignition wiring and ground
wiring.
•
Check all control wiring and connections.
•
Check burner flame pattern (stable and
uniform) and flame.
Additional items if combustion or performance
is poor:
•
Clean baffles and flue ways.
•
Remove burner assembly and clean
burner head using compressed air only.
Once the maintenance items are completed,
review the service with the owner.
Owner Maintenance
Daily:
•
Check the area around the unit.
•
Check the combustion air inlet and ven-
tilation openings for blockage.
•
Check the temperature/pressure gauge.
Monthly:
•
Check vent piping.
•
Check combustion air inlet piping.
•
Check the pressure relief valve.
•
Check the temperature/pressure relief
valve.
•
Check the vent condensate drain system.
•
Check the automatic air vents in the pri-
mary system.
Every 6 months:
•
Check both primary piping and gas
supply piping for corrosion or potential
signs of leakage.
•
Operate the pressure relief valve.
•
Operate the temperature/pressure relief
valve.
Periodically:
•
Check the operation of the domestic
mixing valve.
Follow the maintenance pro c e d u re s
given throughout this manual. Failure
to perform the service and maintenance
or follow the directions in this manual
could result in damage to the PERFOR-
MANCE PLUS or in system compo-
nents, resulting in severe personal
i n j u ry, death or substantial pro p e rt y
damage.