Gas Piping

NATURAL GAS

Pipe Sizing - Natural Gas

1. Refer to Table 3 for pipe length and diame-

ter requirements. Based on rated PER-
FORMANCE PLUS input (divide by 1,000
to obtain cubic feet per hour).

-

Table 3 is based on Natural Gas with a
specific gravity of 0.60 and a pressure
drop through the gas piping of
0.30”w.c..

-

For additional gas piping sizing infor-
mation, refer to ANSI Z223.1. For
Canadian installations refer to B149.1
or B149.2.

Natural Gas Supply Pressure Requirements

1. Pressure required at the gas valve inlet

supply pressure port:

-

Maximum 13”w.c. at flow or no flow
conditions to the burner.

-

Minimum 5”w.c. during flow condi-
tions to the burner. Must be verified
during start up and with all gas appli-
ances operating.

2. Install 100% lockup gas pressure regulator

in the gas supply line if inlet pressure can
exceed 13”w.c at any time. Adjust the lock-
up pressure regulator for 13”w.c maximum.

DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve
is factory-set for the correct outlet pres-
sure. This setting is suitable for natural
gas and propane and requires no field
adjustment. Attempts by the installer to
adjust or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
i n j u ry, death or substantial pro p e rt y
damage.

WARNING

Length of Pipe

in Feet

SCH 40

1/2"

3/4"

1"

1-1/4"

1-1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

860

40

63

130

245

500

760

50

56

115

215

440

670

75

45

93

175

360

545

100

38

79

150

305

460

150

31

64

120

250

380

Capacity of Pipe in Cubic Feet of Gas Per Hour

(based on 0.60 specific gravity, 0.30" w.c. pressure drop)

Table 3: Gas piping sizing - Natural Gas