Venting and combustion air installation – Delta PG PLUS-25 User Manual
Page 39
33
Venting and Combustion Air Installation
The maximum equivalent length is the
total length of the venting and the com-
bustion air inlet combined. This includes
termination fittings.
F o r Delta PERFORMANCE PLUS
applications that may exceed the 100 feet
maximum allowable equivalent length
for the venting system, contact Triangle
Tube Engineering Department for addi-
tional information on how the appliance
can be adjusted to the application.
-
For each elbow included in the system,
the maximum allowable linear length
must be reduced as follows:
• Each 90º elbow within the system is
the equivalent of 10 linear feet.
• Each 45º elbow within the system is
the equivalent of 5 linear feet.
It is recommended that the installer uses the
same number of elbows and length of piping on
the venting system and the combustion air
inlet.
NOTICE
NOTICE
Table 2- Allowable Equivalent Length (Combined Vent and Combustion Air)
Maximum
Allowable for
Linear Length Combined
2
3
4
5
6
7
PERFORMANCE PLUS
180
170
160
150
140
130
Total Elbows within the Venting / Combustion Air System
Fig. 19: Standard Ve rtical Venting Installation
Fig. 20: Ve rtical - Direct Vent Combination