Venting and Combustion Air Installation

The maximum equivalent length is the
total length of the venting and the com-
bustion air inlet combined. This includes
termination fittings.

F o r Delta PERFORMANCE PLUS
applications that may exceed the 100 feet
maximum allowable equivalent length
for the venting system, contact Triangle
Tube Engineering Department for addi-
tional information on how the appliance
can be adjusted to the application.

-

For each elbow included in the system,
the maximum allowable linear length
must be reduced as follows:

• Each 90º elbow within the system is

the equivalent of 10 linear feet.

• Each 45º elbow within the system is

the equivalent of 5 linear feet.

It is recommended that the installer uses the
same number of elbows and length of piping on
the venting system and the combustion air
inlet.

NOTICE

NOTICE

Table 2- Allowable Equivalent Length (Combined Vent and Combustion Air)

Maximum

Allowable for

Linear Length Combined

2

3

4

5

6

7

PERFORMANCE PLUS

180

170

160

150

140

130

Total Elbows within the Venting / Combustion Air System