beautypg.com

Delta PG PLUS-25 User Manual

Page 56

background image

50

Start-Up Preparations

Verify Correct Pressure Switch

1. Remove the burner hood and verify the

burner pressure switch setting.

2. Check and compare the color of the out-

line on the pressure switch label to Table 3
page 49.

The

PERFORMANCE

PLUS

is

equipped with an air pressure switch,
which provides a safe means of shutting
down the unit due to a blockage of the
combustion air inlet. The switch is “nor-
mally closed” and measures the change
in the negative pressure (vacuum) creat-
ed by the burner blower.

Verify Correct Air Shutter Setting

-

Check and verify the air shutter setting
as listed in Table 4.

-

The air shutter is located inside the com-
bustion air inlet adapter located in the
top /left jacket panel area. See Fig. 37.

Check Thermostat Circuit

-

Unplug the Room Thermostat Snap-set
located on the rear of the unit.

-

Connect a voltmeter across the end ter-
minals of the male half of the Room
Thermostat Snap-set.

-

Close each thermostat, zone valve and
relay in the external circuit one zone at
a time and check the voltage reading
across the plug.

-

There should NEVER be voltage mea-
sured at the plug.

-

If voltage is measured at the plug under
any condition, check and correct the
external wiring.

In systems using 3-wire zone valves
backfeed of voltage to the unit is a com-
mon problem. Use an isolation relay to
prevent voltage from the external circuit
entering the Room Thermostat Snap-set.

NOTICE

NOTICE

Model

Natural Gas

Propane

PG PLUS-25

2.5

2.5

PG PLUS-30

2.5

2.5

PG PLUS-35

1

2.0

PG PLUS-40

N/R

0

PG PLUS-45

N/R

0

Table 4 : Air Shutter Settings

NR- Air shutter not required.

Fig. 37: Air Shutter Adjustment

This manual is related to the following products: